Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
7/8 BCN-C22005-639
2 Frequency jump (6-point jump) (Pr.552)
When it is desired to avoid resonance attributable to the natural frequency of a mechanical system, these
parameters allow resonant frequencies to be jumped.
The above parameters can be set when Pr.160 User group read selection = "0".
( Refer to Chapter 4 of the Instruction Manual (Applied) )
(1) Frequency jump (3-point jump) (Pr.31 to Pr.36)
(2) Frequency jump (6-point jump) (Pr.552)
Pr. Name Initial value Setting range Description
31 Frequency jump 1A 9999 0 to 400Hz, 9999
1A to 1B, 2A to 2B, 3A to 3B are frequency
jumps (3-point jump)
9999: Function invalid
32 Frequency jump 1B 9999 0 to 400Hz, 9999
33 Frequency jump 2A 9999 0 to 400Hz, 9999
34 Frequency jump 2B 9999 0 to 400Hz, 9999
35 Frequency jump 3A 9999 0 to 400Hz, 9999
36 Frequency jump 3B 9999 0 to 400Hz, 9999
552 Frequency jump range 9999 0 to 30Hz, 9999
Jump range for the frequency jump (6-point
jump).
9999: 3-point jump
Up to three areas may be set, with the jump frequencies
set to either the top or bottom point of each area.
The value set to 1A, 2A or 3A is a jump point, and
operation in the jump zone is performed at these
frequencies.
Example 1 To fix the frequency to 30Hz in the range of 30Hz to 35Hz, set 35Hz in
Pr.34 and 30Hz in Pr.33.
Example 2 To jump the frequency to 35Hz in the range of 30Hz to 35Hz, set 35Hz in
Pr.33 and 30Hz in Pr.34.
The total of six jump areas can be set by setting the
common jump range for the frequencies set in Pr.31 to
Pr.36.
When frequency jump ranges overlap, the lower limit of
the lower jump range and the upper limit of the upper
jump range are used.
When a frequency is set to a point within a jump range,
the set frequency is lowered or increased to the jump
range limits, according to the following frequency input
condition.
REMARKS
During acceleration/deceleration, the running frequency within the set area is valid.
If the setting ranges of individual groups (1A and 1B, 2A and 2B, 3A and 3B) overlap, Er1 (write disable error) will occur.
Setting Pr.552 = "0" disables frequency jumps.
Pr. 31
Pr. 32
Pr. 33
Pr. 34
Pr. 35
Pr. 36
Frequency jump
Set frequency (Hz)
Pr. 34: 35Hz
Pr. 33: 30Hz
Pr. 33: 35Hz
Pr. 34: 30Hz
Pr.36
Pr.31
0
Pr.32
Pr.34
Pr.33
Pr.35
Set frequency after frequency jump
Input set frequency
Jump range
Jump range
Pr.552
Pr.552
Frequency input
condition
Set frequency after
frequency jump
When accelerating
The setting frequency is decreased to
the lower limit of the jump range.
When decelerating
The setting frequency is increased to
the upper limit of the jump range.