Selection of operation mode and
operation location
4.19.2 Setting the set frequency to operate (example: performing operation at 30Hz)
POINT
Operation panel (FR-DU07) is used to give both of frequency and start commands in PU operation.
Operation example
Performing operation at 30Hz.
Operation Display
1. Screen at power-ON
The monitor display appears.
2. Operation mode setting
Press to choose the PU operation mode.
PU indicator is lit.
3. Running frequency setting
Turn to show the frequency " " (30.00Hz) you
want to set.
The frequency flickers for about 5s.
While the value is flickering, press to set the frequency.
(If you do not press , the value flickers for about 5s and the
display then returns to " " (0.00Hz). At this time, return to
"Step 3" and set the frequency again. After the value flickered for
about 3s, the display returns to " " (monitor display).
Flicker ··· Frequency setting complete!!
After 3s, the monitor display appears.
4. Start → acceleration → constant speed
Press or to start running.
The frequency on the display increases in the Pr. 7 Acceleration
time, and " " (30.00Hz) appears.
/
To change the set frequency, perform the operation in above step 3. (Starting from the previously set frequency.)
5. Deceleration → Stop
Press to stop.
The frequency on the display decreases in the Pr. 8 Deceleration
time, and the motor stops rotating with " " (0.00Hz)
displayed.
Operation panel
(FR-DU07)
PU EXT NET
Flickers for about 5s
Stop