67
Parameter List
Parameter list
4
PARAMETERS
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz 0.01Hz 60Hz 193
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz 0.01Hz 60Hz 193
PID operation
127
PID control automatic switchover
frequency
0 to 400Hz, 9999 0.01Hz 9999 261
128
PID action selection
10, 11, 20, 21, 50, 51, 60,
61, 110, 111, 120, 121
110261
129
PID proportional band 0.1 to 1000%, 9999 0.1% 100% 261
130
PID integral time 0.1 to 3600s, 9999 0.1s 1s 261
131
PID upper limit 0 to 100%, 9999 0.1% 9999 261
132
PID lower limit 0 to 100%, 9999 0.1% 9999 261
133
PID action set point 0 to 100%, 9999 0.01% 9999 261
134
PID differential time 0.01 to 10.00s, 9999 0.01s 9999 261
Bypass
135
Electronic bypass sequence selection 0, 1 1 0 274
136
MC switchover interlock time 0 to 100s 0.1s 1s 274
137
Start waiting time 0 to 100s 0.1s 0.5s 274
138
Bypass selection at a fault 0, 1 1 0 274
139
Automatic switchover frequency from
inverter to bypass operation
0 to 60Hz, 9999 0.01Hz 9999 274
Backlash measures
140
Backlash acceleration stopping
frequency
0 to 400Hz 0.01Hz 1Hz 115
141
Backlash acceleration stopping time 0 to 360s 0.1s 0.5s 115
142
Backlash deceleration stopping
frequency
0 to 400Hz 0.01Hz 1Hz 115
143
Backlash deceleration stopping time 0 to 360s 0.1s 0.5s 115
144
Speed setting switchover
0, 2, 4, 6, 8, 10, 102,
104, 106, 108, 110
14150
PU
145
PU display language selection 0 to 7 1 0 295
147
Acceleration/deceleration time
switching frequency
0 to 400Hz, 9999 0.01Hz 9999 109
Current detection
148
Stall prevention level at 0V input 0 to 150% 0.1% 120% 91
149
Stall prevention level at 10V input 0 to 150% 0.1% 150% 91
150
Output current detection level 0 to 150% 0.1% 120% 146
151
Output current detection signal delay
time
0 to 10s 0.1s 0s 146
152
Zero current detection level 0 to 150% 0.1% 5% 146
153
Zero current detection time 0 to 10s 0.01s 0.5s 146
154
Voltage reduction selection during
stall prevention operation
0, 1 1 1 91
155
RT signal function validity condition
selection
0, 10 1 0 137
156
Stall prevention operation selection 0 to 31, 100, 101 1 0 91
157
OL signal output timer 0 to 25s, 9999 0.1s 0s 91
158
AM terminal function selection
1 to 3, 5, 6, 8 to 14, 17,
21, 24, 50, 52, 53
11152
159
Automatic switchover frequency
range from bypass to inverter
operation
0 to 10Hz, 9999 0.01Hz 9999 274
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page