Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
71
Parameter List
Parameter list
4
PARAMETERS
Communication
549
Protocol selection 0, 1 1 0 247
550
NET mode operation command
source selection
0, 1, 9999 1 9999 219
551
PU mode operation command source
selection
1, 2 1 2 219
PID
operation
553
PID deviation limit 0 to 100.0%, 9999 0.1% 9999 261
554
PID signal operation selection 0 to 3, 10 to 13 1 0 261
Current average
monitor
555
Current average time 0.1 to 1.0s 0.1s 1s 286
556
Data output mask time 0.0 to 20.0s 0.1s 0s 286
557
Current average value monitor signal
output reference current
0 to 500A/0 to 3600A *2 0.01/0.1A *2
Rated
inverter
current
286
563
Energization time carrying-over times (0 to 65535) 1 0 152
564
Operating time carrying-over times (0 to 65535) 1 0 152
571
Holding time at a start 0.0 to 10.0s, 9999 0.1s 9999 113
PID control
575
Output interruption detection time 0 to 3600s, 9999 0.1s 1s 261
576
Output interruption detection level 0 to 400Hz 0.01Hz 0Hz 261
577
Output interruption cancel level 900 to 1100% 0.1% 1000% 261
611
Acceleration time at a restart 0 to 3600s, 9999 0.1s 5/15s *2 162
Speed
smoothing
control
653
Speed smoothing control 0 to 200% 0.1% 0 184
654
Speed smoothing cutoff frequency 0 to 120Hz 0.01Hz 20Hz 184
665
Regeneration avoidance frequency
gain
0 to 200% 0.1% 100 279
779
Operation frequency during
communication error
0 to 400Hz, 9999 0.01Hz 9999
231
791
Acceleration time in low-speed range 0 to 3600/360s, 9999 0.1/0.01s 9999 109
792
Deceleration time in low-speed range 0 to 3600/360s, 9999 0.1/0.01s 9999
109
799
Pulse increment setting for output
power
0.1kWh, 1kWh, 10kWh,
100kWh, 1000kWh
0.1 1kWh 149
800
Control method selection 9, 20 1 20 82
Adjustment
function
820
Speed control P gain 1 0 to 1000% 1% 25% 84
821
Speed control integral time 1 0 to 20s 0.001s 0.333s 84
867
AM output filter 0 to 5s 0.01s 0.01s 157
870
Speed detection hysteresis 0 to 5Hz 0.01Hz 0Hz
144
872
Input phase loss protection selection 0, 1 1 0 175
Regeneration avoidance function
882
Regeneration avoidance operation
selection
0, 1, 2 1 0 279
883
Regeneration avoidance operation
level
300 to 800V 0.1V
380V/
760VDC
*5
279
884
Regeneration avoidance at deceleration
detection sensitivity
0 to 5 1 0 279
885
Regeneration avoidance
compensation frequency limit value
0 to 30Hz, 9999 0.01Hz 6Hz 279
886
Regeneration avoidance voltage gain 0 to 200% 0.1% 100% 279
Function Parameters
Name Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting