Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
222
Selection of operation mode and
operation location
(5) Selection of command source in Network operation mode (Pr. 338, Pr. 339)
There are two control sources: operation command source, which controls the signals related to the inverter start
command and function selection, and speed command source, which controls signals related to frequency setting.
In Network operation mode, the commands from the external terminals and communication (RS-485 terminals or
communication option) are as listed below.
[Explanation of table]
External : Command only from control terminal signal is valid.
NET : Command only from communication is valid
Combined : Command from either of external terminal and communication is valid.
: Command from either of external terminal and communication is invalid.
Compensation : Command by signal from external terminal is only valid when Pr. 28 Multi-speed input compensation selection = "1"
Operation
Location
Selection
Pr. 338 Communication operation command source
0: NET 1: External
Remarks
Pr. 339 Communication speed command source 0: NET
1:External 2:External
0: NET
1:External 2:External
Fixed function
(Terminal-
equivalent
function)
Running frequency from communication
NET
NET NET
NET
Terminal 2
External
⎯⎯
External
Terminal 4
External
External
Terminal 1
Compensation
Selective function
Pr. 178 to Pr. 189 setting
0RL
Low-speed operation command/
remote setting clear
NET External NET External
Pr. 59 = "0" (multi-
speeds)
Pr. 59 = "1 , 2"
(remote)
1RM
Middle-speed operation command/
remote setting deceleration
NET External NET External
2RH
High-speed operation command/
remote setting acceleration
NET External NET External
3 RT Second function selection
NET External
4 AU Terminal 4 input selection
Combined
Combined
5 JOG Jog operation selection
External
6CS
Selection of automatic restart after
instantaneous power failure, flying
start
External
7 OH External thermal relay input
External
8 REX 15-speed selection
NET External NET External
Pr. 59 = "0"
(multi-speeds)
10 X10
Inverter run enable signal
External
11 X11
FR-HC, MT-HC connection,
instantaneous power failure detection
External
12 X12
PU operation external interlock
External
14 X14 PID control valid terminal NET External NET External
16 X16 PU/External operation switchover
External
24 MRS
Output stop
Combined External
Pr. 79
"7"
PU operation interlock
External
Pr. 79 = "7"
When X12 signal
is not assigned
25
STOP
Start self-holding selection
External
60 STF Forward rotation command NET External
61 STR Reverse rotation command NET External
62 RES Inverter reset External
63 PTC PTC thermistor input External
64 X64
PID forward/reverse action
switchover
NET External NET External
65 X65 PU/NET operation switchover
External
66 X66
External/NET operation switchover
External
67 X67 Command source switchover
External
70 X70
DC feeding operation permission
NET External
71 X71
DC feeding cancel
NET External
72 X72
PID integral value reset
NET External NET External
REMARKS
The command source of communication is as set in Pr. 550 and Pr. 551.
The Pr. 338 and Pr. 339 settings can be changed while the inverter is running when Pr. 77 = "2". Note that the setting change is
reflected after the inverter has stopped. Until the inverter has stopped, communication operation command source and
communication speed command source before the setting change are valid.