Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
256
Communication operation and setting
(6) Modbus registers
System environment variable
*1 The communication parameter values are not cleared.
*2 For write, set the data as a control input instruction. For read, data is read as an inverter operating status.
*3 For write, set data as the operation mode setting. For read, data is read as the operation mode status.
Real-time monitor
Refer to page 152 for details of the monitor description.
............... Specifications differ according to the date assembled. Refer to page 378 to check the SERIAL number.
Register Definition Read/Write Remarks
40002 Inverter reset Write Any value can be written
40003 Parameter clear Write Set H965A as a written value.
40004 All parameter clear Write Set H99AA as a written value.
40006 Parameter clear
*1 Write Set H5A96 as a written value.
40007 All parameter clear
*1 Write Set HAA99 as a written value.
40009 Inverter status/control input instruction
*2 Read/write See below.
40010 Operation mode/inverter setting
*3 Read/write See below.
40014 Running frequency (RAM value) Read/write
According to the Pr. 37 and Pr. 144 settings, the
frequency and selectable speed are in 1r/min
increments.
40015 Running frequency (EEPROM value) Write
<Inverter status/control input instruction>
*1 The signal within parentheses is the initial setting. The description changes depending on the setting of Pr. 180 to Pr. 189 (input
terminal function selection) (page133).
Each assigned signal is valid or invalid depending on NET. (Refer to page 219)
*2 The signal within parentheses is the initial setting. The description changes depending on the setting of Pr. 190 to Pr. 196 (output
terminal function selection) (page140).
Bit
Definition
Control input instruction Inverter status
0 Stop command RUN (inverter running) *2
1 Forward rotation command Forward rotation
2 Reverse rotation command Reverse rotation
3 RH (high speed operation command) *1 SU (up to frequency) *2
4 RM (middle speed operation command) *1 OL (overload) *2
5 RL (low speed operation command) *1 IPF (instantaneous power failure) *2
6 JOG (Jog operation) *1 FU (frequency detection) *2
7 RT (second function selection) *1 ABC1 (fault) *2
8 AU (current input selection) *1
ABC2 () *2
9
CS
(selection of automatic restart after
instantaneous power failure)
*1
0
10 MRS (output stop) *1 0
11 STOP (start self-holding) *1 0
12 RES (reset) *1 0
13 0 0
14 0 0
15 0 Fault occurrence
<Operation mode/inverter setting>
* Writing is available depending on the
Pr. 79 and Pr. 340 setting. Refer to page 218
for details.
The restrictions depending on the
operation mode changes according
to the computer link specifications.
Mode
Read
Value
Written
Value
EXT H0000 H0010*
PU H0001 H0011*
EXT
JOG
H0002
PU
JOG
H0003
NET H0004 H0014
PU+
EXT
H0005
Register Description Increments
40201 Output frequency/Speed
*4
0.01Hz/1
40202 Output current
0.01A/0.1A
*1
40203 Output voltage 0.1V
40205
Frequency setting value/Speed
setting
*4
0.01Hz/1
40206 Running speed 1r/min
40208 Converter output voltage 0.1V
40209 Regenerative brake duty 0.1%
40210
Electronic thermal relay function
load factor
0.1%
40211 Output current peak value 0.01A
/0.1A
*1
40212 Converter output voltage peak value 0.1V
40213 Input power
0.01kW/
0.1kW
*1
40214 Output power
0.01kW/
0.1kW
*1
40215 Input terminal status *2
40216 Output terminal status
*3
40217 Load meter
0.1%
40220 Cumulative energization time
1h
40223 Actual operation time
1h
40224 Motor load factor
0.1%
40225 Cumulative power 1kWh
40250 Power saving effect Variable
40251 Cumulative saving power Variable
40252 PID set point
0.1%
40253 PID measured value
0.1%
40254 PID deviation
0.1%
40258 Option input terminal status 1 *5
40259 Option input terminal status 2
*6
40260 Option output terminal status
*7
40267 PID measured value 2 0.1%
40277
32-bit cumulative power
(lower 16 bits)
1kWh
40278
32-bit cumulative power
(upper 16 bits)
1kWh
40279
32-bit cumulative power
(lower 16 bits)
0.01kWh/
0.1kWh
*1
40280
32-bit cumulative power
(upper 16 bits)
0.01kWh/
0.1kWh
*1
Register Description Increments