IPM motor control <IPM>
[IPM motor specification list]
(3) IPM motor control dedicated parameter
The following parameters are activated only under IPM motor control.
See the reference pages for details.
4.3.3 IPM motor test operation (Pr.800)
<IPM>
The above parameters can be set when Pr.160 User group read selection = "0." (Refer to page 201)
(1) Test operation
· To activate the IPM motor test operation, set
Pr.998 IPM parameter initialization
, change the control to IPM motor control,
then set
Pr.800 Control method selection
= "9."
Perform a test operation by giving a frequency and a start command under each of PU/External/Network operation mode.
· P.RUN on the operation panel (FR-DU07) flickers during the IPM motor test operation.
MM-EF
(30kW or lower)
MM-EF
(37kW to 75kW)
MM-EF
(90kW or higher)
MM-EFS
(15kW or lower)
MM-EFS
(18.5kW to 55kW)
Rated motor frequency
(rotations per minute)
90Hz
(1800r/min)
120Hz
(1800r/min)
120Hz
(1800r/min)
75Hz
(1500r/min)
100Hz
(1500r/min)
Maximum motor frequency
(rotations per minute)
135Hz
(2700r/min)
180Hz
(2700r/min)
160Hz
(2400r/min)
112.5Hz
(2250r/min)
150Hz
(2250r/min)
Number of motor poles 6 8 8 6 8
Short-time motor torque 120% 120% 120% 120% 120%
Minimum frequency
(rotations per minute)
9Hz
(180r/min)
12Hz
(180r/min)
12Hz
(180r/min)
7.5Hz
(150r/min)
10Hz
(150r/min)
Speed detection hysteresis
frequency (rotations per minute)
0.5Hz
(10r/min)
0.5Hz
(8r/min)
0.5Hz
(8r/min)
0.5Hz
(10r/min)
0.5Hz
(8r/min)
Parameter
number
Name Description
Refer
to Page
791
Acceleration time in low-
speed range
Acceleration time in the low-speed range ("rated motor frequency/10" or
lower) is set.
109
792
Deceleration time in low-
speed range
Deceleration time in the low-speed range ("rated motor frequency/10" or
lower) is set.
109
800
Control method selection IPM motor test operation is selected. 82
820
Speed control P gain 1
The proportional gain during speed control is set. (Setting this
parameter higher improves the trackability for speed command
changes. It also reduces the speed fluctuation due to a load fluctuation.)
84
821
Speed control integral time 1
The integral time during speed control is set. (Setting this parameter
shortens the return time to the original speed when the speed fluctuates
due to a load fluctuation. )
84
Without connecting an IPM motor, the frequency movement can be checked by the monitor or analog signal output.
Two types of operation can be selected using this parameter: an actual operation by connecting an IPM
motor, or a test operation without connecting an IPM motor to simulate a virtual operation.
Parameter
Number
Name
Initial
value
Setting
range
Operation
800 Control method selection
20
9
IPM motor test operation (Motor is not driven even if
it is connected.)
20 Normal operation (Motor can be driven.)
REMARKS
· In the test operation, current is not detected and voltage is not output. Related monitor displays of the output current and
voltage show "0."
IPM
IPM
IPM
Time
Running frequency
(AM and FM output)
STF
RUN