Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
290
Useful functions
4.22.7 Setting multiple parameters as a batch (Pr.999)
* This parameter allows its setting to be changed in any operation mode even if "0 (initial value)" is set in Pr. 77 Parameter write selection.
(1) Automatic parameter setting (Pr.999)
Select which parameters to be automatically set, and set that to Pr. 999. Multiple parameter settings are changed
automatically. Refer to page 293 for the list of parameters that are changed automatically.
Parameter settings are changed as a batch. Those include communication parameter settings for the
Mitsubishi human machine interface (GOT) connection, rated frequency settings of 50Hz/60Hz, and
acceleration/deceleration time increment settings.
Multiple parameters are changed automatically. Users do not have to consider each parameter number.
(Parameter setting mode)
Parameter
Number
Name Initial value Setting range Description
999 * Automatic parameter setting 9999
10 GOT initial setting (PU connector)
11 GOT initial setting (RS485 terminals)
20 50Hz rated frequency
21 60Hz rated frequency
30
Acceleration/deceleration time
(0.1s increment)
31
Acceleration/deceleration time
(0.01s increment)
9999 No action
Pr.999 setting Description
Operation in the parameter setting
mode
10
Automatically sets the communication parameters for the GOT
connection with a PU connector
"AUTO" "GOT" Write "1"
11
Automatically sets the communication parameters for the GOT
connection with RS-485 terminals
20
50Hz rated
frequency
Sets the related parameters of the rated
frequency according to the power supply
frequency
"AUTO" "F50" Write "1"
21
60Hz rated
frequency
30 0.1s increment
Changes the setting increments of
acceleration/deceleration time parameters
without changing acceleration/deceleration
settings
31 0.01s increment "AUTO" "T0.01" Write "1"
REMARKS
If the automatic setting is performed, the selected settings including the changed parameter settings will be changed.