Selection of operation mode and
operation location
4.19 Selection of operation mode and operation location
4.19.1 Operation mode selection (Pr. 79)
The above parameters can be changed during a stop in any operation mode.
*1 This parameter allows its setting to be changed in any operation mode even if "0 (initial value) or 1" is set in Pr. 77 Parameter write selection.
*2 The priorities of the frequency commands when Pr. 79 = "3" are "Multi-speed operation (RL/RM/RH/REX) > PID control (X14) > terminal 4 analog
input (AU) > digital input from the operation panel".
Purpose Parameter that must be set Refer to page
Operation mode selection Operation mode selection Pr. 79 206
Started in network operation mode Operation mode at power ON Pr. 79, Pr. 340 218
Selection of operation location
Selection of start command source, speed
command source and operation location
during communication operation
Pr. 338, Pr. 339,
Pr. 550, Pr. 551
219
Used to select the operation mode of the inverter.
Mode can be changed as desired between operation using external command signals (external operation), operation
from the PU (FR-DU07/FR-PU04/FR-PU07), combined operation of PU operation and external operation (external/PU
combined operation, and network operation (when RS-485 terminals or a communication option is used).
Parameter Number Name Initial Value Setting Range
79 Operation mode selection
0 0 to 4, 6, 7
POINT
• Use the easy setting mode to set Pr. 79 in simple steps. (Refer to page 62)
Pr.79
Setting
Description
LED Indication
: OFF : ON
Refer
to
page
0
Use External/PU switchover mode
Press to switch between the PU and External operation mode.
At power ON, the inverter is in the External operation mode.
PU operation mode
External operation mode
NET operation mode
209
1
Operation mode Frequency command Start command
PU operation mode
209
PU operation mode (fixed)
Setting by the operation
panel (FR-DU07) and PU
(FR-PU04/FR-PU07)
Input by and on
PU (FR-DU07/FR-PU04/FR-
PU07)
2
External operation mode (fixed)
The operation can be performed
by switching between the
External and NET operation
modes.
External signal input (from
terminal 2, 4, and 1, JOG,
multi-speed selection, etc.)
External signal input (from
terminal STF and STR)
External operation mode
NET operation mode
209
3
External/PU combined
operation mode 1
PU (FR-DU07/FR-PU04/FR-
PU07) setting or external
signal input (multi-speed
setting, across terminals 4
and 5 (valid when AU signal
turns ON)).
*2
External signal input (from
terminal STF and STR)
External/PU combined
operation mode
210
4
External/PU combined
operation mode 2
External signal input
(Terminal 2, 4, 1, JOG, multi-
speed selection, etc.)
Input by and on
PU (FR-DU07/FR-PU04/FR-
PU07)
210
6
Switchover mode
Switch among PU operation, External operating, and NET operation while keeping the
same operating status.
PU operation mode
External operation mode
NET operation mode
211
7
External operation mode (PU operation interlock)
X12 signal ON: Operation mode can be switched to the PU operation mode.
(output stop during External operation)
X12 signal OFF: Operation mode cannot be switched to the PU operation mode.
211
REMARKS
If switching of the operation mode is invalid even though Pr. 79 is set, refer to 5.5.9 Operation mode is not changed properly (page 327).