Mitsubishi Electronics FR-F720P Marine Battery User Manual


 
16
Main circuit terminal specifications
2.2 Main circuit terminal specifications
2.2.1 Specification of main circuit terminal
2.2.2 Terminal arrangement of the main circuit terminal, power supply and the motor
wiring
200V class
Terminal
Symbol
Terminal Name Description
Refer to
Page
R/L1,
S/L2,
T/L3
AC power input
Connect to the commercial power supply.
Keep these terminals open when using the high power
factor converter (FR-HC, MT-HC) or power regeneration
common converter (FR-CV).
16
U, V, W Inverter output
Connect a three-phase squirrel-cage motor or dedicated
IPM motor.
16
R1/L11,
S1/L21
Power supply for
control circuit
Connected to the AC power supply terminals R/L1 and S/
L2. To retain the fault display and fault output or when
using the high power factor converter (FR-HC, MT-HC) or
power regeneration common converter (FR-CV), remove
the jumpers from terminals R/L1 and R1/L11, and S/L2
and S1/L21, and apply external power to these terminals.
The power capacity necessary when separate power is
supplied from R1/L11 and S1/L21 differs according to the
inverter capacity.
24
P/+, N/-
Brake unit
connection
Connect the brake unit (FR-BU2, FR-BU, BU and MT-
BU5), power regeneration common converter (FR-CV),
high power factor converter (FR-HC and MT-HC) or power
regeneration converter (MT-RC).
34
P/+, P1
DC reactor
connection
For the 55K or lower, remove the jumper across terminals
P/+ and P1, and connect the DC reactor. (Be sure to
connect the DC reactor supplied with the 75K or higher.)
When a DC reactor is not connected, the jumper across
terminals P/+ and P1 should not be removed.
42
PR, PX Please do not remove or use terminals PR and PX or the jumper connected.
Earth (ground)
For earthing (grounding) the inverter chassis. Must be
earthed (grounded).
22
FR-F720P-0.75K, 1.5K FR-F720P-2.2K to 5.5K
15K or lower 18.5K 22K or higher
200V class 60VA 80VA 80VA
400V class 60VA 60VA 80VA
R/L1
S/L2
T/L3
N/-
P/+
PR
PX
R1/L11
S1/L21
Charge lamp
As this is an inside cover fixing screw,
do not remove it.
Jumper
Screw size (M4)
Screw size
(M4)
Jumper
Motor
Power supply
M
R/L1 S/L2 T/L3
N/-
P/+
PR
PX
R1/L11 S1/L21
M
Charge lamp
Jumper
Screw size (M4)
Screw size
(M4)
Jumper
Motor
Power
supply