Special registers
D9018
Scan time
(10ms units)
Stores and updates the scan time at every END in
BIN.
D9019
Maximum scan
time
(10ms units)
Stores the scan time at every END that is greater than
D9019 data, i.e. stores the maximum scan time in
BIN.
Special registers for control
D9133
Output frequency
monitor
Stores the current output frequency.
0.01Hz units
117D9134
Output current
monitor
Stores the current output current.
0.01A units
D9135
Output voltage
monitor
Stores the current output voltage.
0.1V units
D9136 Error history 1, 2
Store the errors that occurred in the inverter in order
of occurrence.
117
D9137 Error history 3, 4
D9140
Operation mode
setting read
Stores the current operation mode. 119
D9141
Set frequency
read (RAM)
Reads and stores the set frequency (RAM). 120
D9142
Set frequency
read (E
2
PROM)
Reads and stores the set frequency (E
2
PROM).
120
D9143
Operation mode
setting write
Sets a new operation mode. 122
D9144
Set frequency
write (RAM)
Sets the running frequency (RAM). 123
D9145
Set frequency
write (E
2
PROM)
Sets the running frequency (E
2
PROM).
124
D9146
Alarm definition
batch clear
Write H9696 to clear the error history. 125
D9147 Parameter clear
H9696 write: Parameter clear
H9966 write: All clear
H5A5A write:Parameter clear except communication
parameters
H55AA write:All clear except communication
parameters
125
D9148
Inverter operation
status control
Turn on/off the corresponding bits to control the
inverter operation status.
126
D9149
Inverter operation
status control
enable/disable
setting
Enable/disable the inverter operation status control
using D9148 by turning on/off the corresponding bits.
127
D9150
Inverter
parameter
access error
Stores the error No. when an error occurs because
the data stored in the parameter or special register is
not reflected on the inverter.
128
D9151 Inverter status
Stores the running status and operating status of the
inverter.
128
D9062 to
D9069
Remote registers
Special registers for communication with the master
station in CC-Link.
Refer to page 145 for details.
Number Name Description Page