Mitsubishi Electronics FR-C500 Marine Radio User Manual


 
53
Function (Parameter) List
Parameter List
3
INVERTER FUNCTIONS
Computer link
338
Operation control
command source
(CC-Link)
0: Command source
from CC-Link
1: Command source
from external
terminal
1076
339
Speed command
source
(CC-Link)
0: Command source
from CC-Link
1: Command source
from external
terminal
1076
340
Link start up mode
selection
(CC-Link)
0: As set in Pr. 79
1: Started in CC-Link
operation mode
1076
341 CR/LF selection
0: Without CR/LF
1: With CR, without LF
2: With CR/LF
1179
342
E
2
PROM write
selection
0: Write to RAM and
E
2
PROM
1: Write to RAM only
1092
CC-Link
503
CC-Link station
number setting
Set the station number
for inverter/CC-Link
operation.
1 to 64
11143
504
CC-Link baudrate
setting
Set the baudrate for
CC-Link operation.
0:156kbps 1:625kbps
2:2.5Mbps 3:5Mbps
4:10Mbps
10143
Sequence
SQ terminal
function selection
0:RL, 1:RM, 2:RH,
6:MRS, 7:OH, 10:RES,
50:SQ, 9998: No
function
15068
ALM terminal
function selection
0:RUN, 3:OL, 99:ALM,
9998: No function
19969
507
Inverter operation lock
mode setting
0: STF and STR
commands are valid
regardless of RUN/
STOP of the
sequence.
1: STF and STR
commands are valid
only during RUN of
the sequence, and
invalid during STOP.
10138
510
to
529
User parameters 1 0 135
530 Forced I/O selection
1: CC-Link remote input
2: CC-Link remote output
3: Control input
terminal (external)
4: Control output
terminal (external)
9999: Function invalid
1 9999 136
Func
tion
Para-
meter
Name Setting Range
Minimum
Setting
Increme
nts
Factory
Setting
Refer
ence
Page
Custo
mer
Setting
505
506