Errors (Alarms)
PROTECTIVE FUNCTIONS
6
6.1.1 Error (alarm) definitions
(1) Major failures
When the protective function is activated, the inverter output is shut off and an alarm is
output.
Operation Panel
Indication
0C1 FR-PU04 OC During Acc
Name Overcurrent shut-off during acceleration
Description
When the inverter output current reaches or exceeds approximately 200%
of the rated inverter current during acceleration, the protective circuit is
activated to stop the inverter output.
Check point
Check for too slow acceleration.
Check for output short-circuit/ground fault.
Corrective action Decrease the acceleration time.
Error code H10
Operation Panel
Indication
0C2 FR-PU04 Stedy Spd OC
Name Overcurrent shut-off during constant speed
Description
When the inverter output current reaches or exceeds approximately 200%
of the rated inverter current during constant speed operation, the protective
circuit is activated to stop the inverter output.
Check point
Check for sudden load change.
Check for output short-circuit/ground fault.
Corrective action Keep load stable.
Error code H11
Operation Panel
Indication
0C3 FR-PU04 OC During Dec
Name Overcurrent shut-off during deceleration
Description
When the inverter output current reaches or exceeds approximately 200%
of the rated inverter current during deceleration (other than acceleration or
constant speed), the protective circuit is activated to stop the inverter
output.
Check point
Check for sudden speed reduction.
Check for output short-circuit/ground fault.
Check for too fast operation of the motor's mechanical brake.
Corrective action
Increase the deceleration time.
Adjust brake operation.
Error code H12