16
Input Terminals
*1: Also stopped by the key. Refer to page 71.
Start/Stop Timing Chart
Forward-Reverse Rotation Switch-Over Timing Chart
DC Injection Brake and Coasting to Stop
Operation
Mode
External Operation
Pr. 79= "0", "2", "3"
PU Operation
Pr. 79= "0", "1", "4"
DC
Injection
Brake
Terminals STF
(STR)-SD
disconnected (*1)
Set frequency
changed to 0Hz
Stop key
Set frequency
changed to
0Hz
DC injection
brake
enabled
DC injection brake
operated at not
more than "DC
injection brake
operation frequency"
set in Pr. 10
DC injection
brake operated at
0.5Hz or less.
DC injection brake
operated at not more
than "DC injection
brake operation
frequency" set in Pr. 10
DC injection
brake operated
at 0.5Hz or less.
DC injection
brake
disabled
Coasted to a stop at
not more than "DC
injection brake
operation frequency"
set in Pr. 10
Coasted to a stop
at 0.5Hz or less.
Coasted to a stop at
not more than "DC
injection brake
operation frequency"
set in Pr. 10
Coasted to a
stop at 0.5Hz or
less.
REMARKS
*1. The "starting frequency" in Pr. 13 (factory-set to 0.5Hz) may be set between 0 and 60Hz.
*2. If the next start signal is given during DC injection brake operation, the DC injection brake
is disabled and restart is made.
*3. The "DC injection brake operation time" in Pr. 11 (factory-set to 0.5s) may be set between 0 and 10s.
*4. The frequency at which the motor is coasted to a stop is not more than the "DC injection
brake operation frequency" set in Pr. 10 (factory setting = 3Hz; may be set between 0 and
120Hz) or not more than 0.5Hz.
*5. The "starting frequency" in Pr. 13, "DC injection brake operation time" in Pr. 11 and "DC
injection brake operation frequency" in Pr. 10 are the factory-set values.
STOP
RESET
0.5Hz
ON
(*2)
3Hz
0.5s
0.5Hz
0.5s
ON
0.5Hz
ON
3Hz
(*4)
DC injection brake enabled DC injection brake disabled
Output frequency
Starting frequency
Pr. 13
(*1)
DC injection brake
operation
frequency Pr. 10
DC injection brake not operated
Coasted to
a stop
Time
Start
signal
terminal
Across STF-SD
Across STR-SD
DC injection
brake operation
time Pr. 11 (*3)
DC injection
brake operation
time Pr. 11 (*3)
0.5Hz
3Hz
3Hz
(*4)
0.5s
ON
ON ON
ON
0.5Hz
Output frequency
Starting
frequency
Pr.13
(*1)
Start signal switched on while
DC injection brake is being
operated
Forward
rotation
DC injection brake operation
frequency Pr. 10
DC injection brake
enabled
Time
Start
signal
terminal
Across
STR-SD
Across
STF-SD
Reverse
rotation
DC injection brake operation
time Pr. 11 (*3)
Forward
rotation