Function (Parameter) List
Parameter List
Operation selection
77*
Parameter write
disable selection
0: Write enabled only
during stop
1: Write disabled
(except some)
2: Write enabled
during operation
1074
79
Operation mode
selection
0: PU/external
switchable
1: PU 2: External
3: External/PU
combined
4: External/PU
combined
1075
FR-PU04
145
PU display
language
selection
0: Japanese
1: English
2: German
3: French
4: Spanish
5: Italian
6: Swedish
7: Finish
1093
Computer link
331
RS-485
communication
station number
setting
0 to 31: Specify the
station
number of the
inverter.
1079
332
RS-485
communication speed
48:4800bps,
96:9600bps
192:19200bps
19679
333 Stop bit length
0: Data length 8,
stop bit 1
1: Data length 8,
stop bit 2
10: Data length 7,
stop bit 1
11: Data length 7,
stop bit 2
1079
334
Parity check
presence/absence
0: Absence
1: With odd parity
check
2: With even parity
check
1179
335
Number of
communication retries
0 to 10, 9999 1 1 79
336
Communication check
time interval
0 to 999s, 9999 0.1s 9999 79
337 Waiting time setting 0 to 150ms, 9999 1 9999 79
Func
tion
Para-
meter
Name Setting Range
Minimum
Setting
Increme
nts
Factory
Setting
Refer
ence
Page
Custo
mer
Setting
indicates the communication parameters. Note them when clearing the parameters.
(Refer to pages 89, 125.)