Mitsubishi Electronics FR-C500 Marine Radio User Manual


 
178
Ratings
7.1 Ratings
(1) 3-phase 200V power supply
*1. The applicable motor capacity indicated is the maximum applicable capacity when a
Mitsubishi 4-pole standard motor is used.
*2. The rated output capacity indicated assumes that the output voltage is 230V.
*3. The % value of the overload capacity indicates the ratio of the overload current to the
inverter's rated current. For repeated duty, allow time for the inverter and motor to return
to or below the temperatures under 100% load.
*4. The maximum output voltage cannot exceed the power supply voltage.
The maximum output voltage may be set as desired below the power supply voltage.
However, the PWM pulse voltage value of the inverter output side voltage remains
unchanged at about that of the power supply.
*5. The power supply capacity changes with the values of the power supply side inverter
impedances (including those of the input reactor and cables).
Type FR-C520-%K 0.1 0.2 0.4 0.75 1.5 2.2 3.7
Applicable motor capacity (kW) (*1) 0.1 0.2 0.4 0.75 1.5 2.2 3.7
Output
Rated capacity (kVA) (*2) 0.3 0.5 1.0 1.6 2.8 4.0 6.6
Rated current (A) 0.8 1.4 2.5 4.1 7.0 10 16.5
Overload capacity (*3) 150% 60s, 200% 0.5s (inverse time characteristics)
Voltage (*4) Three phase, 200V to 240V 50Hz/60Hz
Power supply
Rated input AC voltage,
frequency
Three phase, 200V to 240V 50Hz/60Hz
Permissible AC voltage
fluctuation
170 to 264V 50Hz/60Hz
Permissible frequency
fluctuation
Within ±5%
Power supply system capacity
(kVA) (*5)
0.4 0.7 1.2 2.1 4.0 5.5 9
Protective structure (JEM 1030) Open type (IP00)
Cooling system Self-cooling Forced air cooling
Approx. weight (kg) 0.5 0.5 0.7 0.9 1.4 1.4 2.1
2