Operation Selection Function Parameters
!
!!
! Setting of running frequency and start command source (Pr. 338,
Pr. 339)
Set the following parameters when you want to give a running frequency or start
command using the signal connected to the external terminal in the CC-Link
operation mode.
(Refer to page 68 for Pr. 60 to Pr. 63, Pr. 65, Pr. 505 (input terminal function
selection).)
[Explanation of table]
External : Operation is valid only from external terminal signal.
CC-Link : Operation is valid from PLC via CC-Link.
Combined : Operation is valid from either of external terminal and CC-Link
communication.
External and CC-Link: Operation is valid under AND condition of external terminal
input and CC-Link input.
Operation
location
selection
Pr. 338 "operation command
source"
0:
CC-Link
0:
CC-Link
1:
External
1:
External
Pr. 339 "speed command
source"
0:
CC-Link
1:
External
0:
CC-Link
1:
External
Selection function
Pr. 60 to Pr. 63, Pr. 65, Pr. 505 settings
0
Low-speed operation
command (RL)
CC-Link External CC-Link External
1
Middle-speed operation
command (RM)
CC-Link External CC-Link External
2
High-speed operation
command (RH)
CC-Link External CC-Link External
6 Output stop (MRS)
Combined Combined External External
7
External thermal relay
input (OH)
External External External External
10 Reset (RES)
Combined Combined Combined Combined
17
Forward rotation
command (STF)
CC-Link CC-Link External External
50 Sequence start (SQ)
External
and
CC-Link
External
and
CC-Link
External External
9999
Reverse rotation
command (STR)
CC-Link CC-Link External External
MRS selection
function
PU operation interlock
(MRS)
External External External External
Related parameters
Pr. 75 "PU stop selection" (Refer to page 71.)
Pr.145 Refer to page 93.