CC-Link I/O Specifications
<I/O word data>
Remote registers (master station
inverter): RWw0 to RWw3
Special registrars of built-in PLC function: D9062 to D9065
Remote registers (inverter master station): RWr0 to RWr3
Special registrars of built-in PLC function: D9066 to D9069
Device No. Name Description Remarks
D9062 Remote register RWw0 Registers designed to read data
received from the master station.
Received data are read to D9062 to
D9065 automatically.
User area
D9063 Remote register RWw1
D9064 Remote register RWw2
D9065 Remote register RWw3
D9066 Remote register RWr0 Registers designed to write data to
be sent to the master station.
Data transmission from D9066 to
D9069 is made automatically.
User area
D9067 Remote register RWr1
D9068 Remote register RWr2
D9069 Remote register RWr3
REMARKS
Use the remote registers freely since they are all user areas.
Devices in CC-Link (station No. 1)
RY00 to 0F
RX00 to 0F
RWw0
RWw1
RWw2
RWw3
RWr0
RWr1
RWr2
RWr3
Devices in built-in sequence
X10 to 1F
Y10 to 1F
D9062
D9063
D9064
D9065
D9065
D9066
D9067
D9068
Automatically refreshed at every END.
FR-C500 series
Master station