159
Errors (Alarms)
PROTECTIVE FUNCTIONS
6
(2) Minor failure
When the protective function is activated, the output is not shut off.
(3) Warnings
When the protective function is activated, the output is not shut off.
*4. The stall prevention operation current can be set as desired. It is factory-set to
150%.
Operation Panel
Indication
CPU FR-PU04 CPU Fault
Name CPU error
Description
If the arithmetic operation of the built-in CPU does not end within a
predetermined period, the inverter self-determines it as an alarm and stops
the output.
Check point
Corrective action Please contact your sales representative.
Operation Panel
Indication
FN FR-PU04 FN
Name Fan trouble
Description
For the inverter that contains a cooling fan, appears on the operation
panel when the cooling fan stops due to a fault or different operation from
the setting of Pr. 76 "cooling fan operation selection".
Check point Check the cooling fan for a fault.
Corrective action Replace the fan.
Operation Panel
Indication
OL FR-PU04 OL
Name Stall prevention (overcurrent)
Description
During
acceleration
If a current of more than 150% (*4) of the rated inverter
current flows in the motor, this function stops the increase in
frequency until the overload current reduces to prevent the
inverter from resulting in overcurrent shut-off. When the
overload current has reduced below 150%, this function
increases the frequency again.
During
constant-
speed
operation
If a current of more than 150% (*4) of the rated inverter
current flows in the motor, this function lowers the frequency
until the overload current reduces to prevent overcurrent
shut-off. When the overload current has reduced below
150%, this function increases the frequency up to the set
value.
During
deceleration
If a current of more than 150% (*4) of the rated inverter
current flows in the motor, this function stops the decrease in
frequency until the overload current reduces to prevent the
inverter from resulting in overcurrent shut-off. When the
overload current has reduced below 150%, this function
decreases the frequency again.
Check point Check the motor for use under overload.
Corrective action
The acceleration/deceleration time may change.
Increase the stall prevention operation level with Pr. 22 "stall prevention
operation level", or disable stall prevention with Pr. 21 "stall prevention
function selection".
Check that the torque boost (Pr. 0) setting is not higher than required.