CC-Link Parameters
5
CC-Link COMMUNICATION
5.2 CC-Link Parameters
5.2.1 Setting of station number and baudrate (Pr. 503, Pr. 504)
Set the station number and communication baurdrate of CC-Link communication.
5.2.2 Regarding the operation mode
When performing CC-Link operation, choose the operation mode other than the PU
operation mode (set 0 or 2 in Pr. 79).
Set "1" in Pr. 340 "link start up mode selection" or set "H0000" in device D9140
"operation mode selection read". (Refer to page 76.)
In the CC-Link operation mode, the PU and EXT LEDs flicker slowly. (Refer to page
44.)
Parameter Name
Setting
Range
Factory
Setting
Remarks
503 CC-Link station number setting 1 to 64 1
504 CC-Link baudrate setting 0 to 4 0
0: 156kbps
1: 625kbps
2: 2.5Mbps
3: 5Mbps
4: 10Mbps
POINT
If you have changed either or both of these parameter settings, perform the
power-on reset or reset of the inverter. (Refer to page 161 for reset.)
REMARKS
Refer to page 43 for checking operation.
POINT
To start the inverter's built-in PLC in the CC-Link operation mode, short
external input terminals SQ-SD and also turn on the remote output device RY5
(SQ terminal) from the master station.