Mitsubishi Electronics FR-C500 Marine Radio User Manual


 
122
Inverter Status Monitoring, Special Registers for
Control
(1) Operation mode setting write (D9143)
Data are as follows:
H0000: CC-Link operation mode
H0001: External operation mode
H0002: PU operation mode
The operation mode switching method is as shown below when the Pr. 79
"operation mode selection" value is "0".
<When Pr. 79=2, switching is performed as shown below.>
There are no restrictions on operation mode switching.
On normal completion of operation mode setting, the write completion signal
(X23) turns on, and at the same time, 0 is set to D9150.
If the value written is other than H0000 to H0002 or write is performed during
inverter operation, HFFFF is set to D9150 as soon as the write completion signal
(X23) turns on, resulting in abnormal completion.
If abnormal completion occurs, the operation mode is not changed.
<Operation mode setting write program example>
The following program changes the operation mode to the NET mode.
REMARKS
When Pr. 79 is other than 0, the mode is fixed.
H0001
H0000
H0002
H0001
(CC-Link)
H0002
H0000
NET mode
External
operation mode
PU operation
mode
H0001
H0000
(CC-Link)
NET mode External
operation mode
Operation mode write setting request
Normal write
Abnormal write
Turns on operation mode
setting write request pulse.
Check whether operation mode
setting write completion signal
turned on to judge whether write
was performed normally or not.
Stores 0 (CC-Link operation mode)
to D9143 and turns on operation
mode setting write command.
(Until completion signal turns on)