Mitsubishi Electronics FR-C500 Marine Radio User Manual


 
132
Inverter Parameter Read/Write Method
4.8.2 Writing the inverter parameters
When data are stored into the corresponding registers of the inverter parameters
(refer to page 110) and the parameter write command is turned from off to on, the data
are written to the parameters that are the targets of all device data. (After that, the
write completion is turned on.)
As soon as the inverter parameter write completion (X29 (RAM) or X2B (E
2
PROM))
turns on, 0 is set to D9150 on normal completion.
If an error occurs during access to the parameters, e.g. if any value outside the setting
range is written or write is performed during inverter operation, the value of parameter
No. + H8000 is set to D9150 as soon as the write completion signal (X29 (RAM) or
X2B (E
2
PROM)) turns on, resulting in abnormal completion. If abnormal completion
occurs, the parameters are not written. (For example, if an error occurs in the torque
boost, H8000 is written to D9150.)
For whether inverter parameter write can be performed or not, refer to Pr. 77
"parameter write disable selection" (page 74).
Command Device No.
Parameter write command (RAM) Y29
Parameter write completion (RAM) X29
Parameter write command (E
2
PROM)
Y2B
Parameter write completion (E
2
PROM)
X2B
POINT
Inverter parameter write must be performed in the PU operation mode and CC-
Link operation mode. (Refer to page 75.)