Mitsubishi Electronics FR-C500 Marine Radio User Manual


 
188
Instructions for Compliance with the European Standards
(2) Low Voltage Directive
1) Our view of transistorized inverters for the Low Voltage Directive
Transistorized inverters are covered by the Low Voltage Directive (Standard to
conform to: EN50178).
2) Compliance
We have self-confirmed our inverters as products compliant to the Low Voltage
Directive and place the CE mark on the inverters.
3) Outline of instructions
* Connect the equipment to the earth securely. Do not use an earth leakage circuit
breaker as an electric shock protector without connecting the equipment to the
earth.
* Wire the earth terminal independently. (Do not connect two or more cables to one
terminal.)
* Use the cable sizes on pages 6 under the following conditions.
Ambient Temperature: 40°C maximum
Wire installation: On wall without ducts or conduits
If conditions are different from above, select appropriate wire according to EN60204
ANNEX C TABLE 5.
* Use the no-fuse breaker and magnetic contactor which conform to the EN or IEC
Standard.
* Use the breaker of type B (breaker which can detect both AC and DC). If not,
provide double or enhanced insulation between the inverter and other equipment,
or put a transformer between the main power supply and inverter.
* Use the inverter under the conditions of overvoltage category II and contamination
level 2 or higher specified in IEC664.
* On the input and output of the inverter, use cables of the type and size set forth in
EN60204 Appendix C.
* The terminals indicated as the control circuit input and output terminals on page 8
are separated safely from the main circuit.
* Environment´
Details are given in the technical information "Low Voltage Directive Conformance
Guide" (BCN-A21041-203). Please contact your sales representative.
During operation In storage
During
transportation
Ambient
Temperature
-10°C to +50°C-20°C to +65°C -20°C to +65°C
Ambient
Humidity
90% RH or less 90% RH or less 90% RH or less
Muximum
Altitude
1000m 1000m 10000m