Operation Selection Function Parameters
3
INVERTER FUNCTIONS
3.6.6 Operation mode and command source (Pr. 79, Pr. 338,
Pr. 339, Pr. 340)
In the following table, operation using the operation panel, parameter unit or RS-485
communication is abbreviated to PU operation.
Used to select the operation mode, operation command source and speed
command source of the inverter.
The inverter can be run from the operation panel or parameter unit or by RS-485
communication (PU operation), with external signals (external operation), and by
CC-Link communication (CC-Link operation).
The inverter is placed in the external operation mode at power-on (factory setting).
Parameter Name Factory Setting Setting Range
79 Operation mode selection 0 0 to 4
338
Operation command source
(CC-Link)
00, 1
339 Speed command source (CC-Link) 0 0, 1
340
link start up mode selection (CC-
Link)
00, 1
Pr. 79 Setting Function
0
(Factory
setting)
At power-on, the inverter is put in the external operation mode.
The operation mode can be changed between the PU and external operation
modes from the operation panel ( key) or parameter unit ( / key).
For each mode, refer to the columns of settings 1 and 2.
1
Operation mode Running frequency Start command
PU operation mode
Digital setting of FR-PU04
RS-485 communication
Sequence program
Operation panel
( key)
FR-PU04 (FWD/REV key)
RS-485 communication
2
External operation
mode
External RH, RM, RL signals
(Three-speed setting)
External STF/STR signal
3
External/PU
combined operation
mode 1
Digital setting of FR-PU04
RS-485 communication
Sequence program
External RH, RM, RL signals
External STF/STR signal
4
External/PU
combined operation
mode 2
External RH, RM, RL signals
(Three-speed setting)
Operation panel
( key)
FR-PU04 (FWD/REV key)
RS-485 communication
REMARKS
A stop function (PU stop selection) by
key of the
operation panel or PU (FR-PU04) is
made valid during operation other than the PU operation mode.
(Refer to page 71.)
PU
EXT
PU
EXT
RUN
RUN
STOP
RESET