Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
101
3
PARAMETERS
Description of parameters
(4) Data definitions
1) Control code
2) Station number
Specify the station number of the converter which communicates with the computer.
3) Instruction code
Specify the processing request, e.g. operation or monitoring, given by the computer to the converter. Hence, the
converter can be run and monitored in various ways by specifying the instruction code appropriately. (Refer to page
106)
4) Data
Indicates the data such as frequency and parameters transferred to and from the converter. The definitions and
ranges of set data are determined in accordance with the instruction codes. (Refer to page 106)
5) Waiting time
Specify the waiting time between the receipt of data at the converter from the computer and the transmission of reply
data. Set the waiting time in accordance with the response time of the computer in the range of 0 to 150ms in 10ms
increments. (Example; 1:10ms, 2:20ms)
6) Sum check code
The sum check code is a 2-digit ASCII (hexadecimal) representing the lower 1 byte (8 bits) of the sum (binary)
derived from the checked ASCII data.
Signal
Name
ASCII Code Description
STX H02 Start Of Text (Start of data)
ETX H03 End Of Text (End of data)
ENQ H05 Enquiry (Communication request)
ACK H06 Acknowledge (No data error detected)
LF H0A Line Feed
CR H0D Carriage Return
NAK H15 Negative Acknowledge (Data error detected)
REMARKS
When Pr. 123 (waiting time setting) 9999, create the communication request data without "waiting time" in the data format. (The
number of characters decreases by 1.)
The data check time varies by the instruction code. (Refer to page 102)
Computer
Converter
Converter
Computer
Converter data processing time
=+
Waiting time
(setting 10ms)
data check time
(About 10 to 30ms,
which depends on the
instruction code)
(Example 1)
Computer Converter
ENQ
*Waiting
time
1
Instruction
code
Station
number
0
1
Data
E1 07ADF4
H05 H30 H31 H31H45 H31 H30 H37 H41 H44 H46 H34
Binary code
H30+H31+H45+H31+H31+H30+H37+H41+H44
= H1F4
Sum
(Example 2)
STX
Data read
Station
number
0
117 0 30
H02 H30 H31 H37H31 H37 H30 H03 H33 H30
Sum
ETX
7
* When the Pr. 123 Waiting time setting "9999", create the communication request
data without "waiting time" in the data format.
(The number of characters decreases by 1.)
Converter
ASCII Code
ASCII Code
Binary code
H30+H31+H31+H37+H37+H30
= H130
Sum
check
code
Sum
check
code
Computer
HC2.book 101 ページ 2012年11月19日 月曜日 午前10時52分