Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
74
Parameter list
 Differ according to capacities. (55K or lower/75K or higher)
 Differs according to the voltage class. (200V class/400V class)
 Parameters which can be set when the plug-in option (FR-A7NC) is mounted.
 The setting is applied after converter reset or at the next power-ON.
 "L.ERR" LED on FR-A7NC flickers when a setting is changed. If the converter is reset, the setting is applied and LED turns off.
 The parameter number in parentheses is the one for use with the parameter unit (FR-PU07).
56 Current monitoring reference
0 to 500A/0 to 3600A
0.01A/
0.1A

Rated
current
84
57 Restart selection 0, 9999 1 9999 89
58 Free parameter 1 0 to 9999 1 9999 90
59 Free parameter 2 0 to 9999 1 9999 90
61 Key lock operation selection 0, 10 1 0 90
65 Retry selection 0, 1, 2, 3, 4 1 0 91
67 Number of retries at fault occurrence 0 to 10, 101 to 110 1 0 91
68 Retry waiting time 0.1 to 360s 0.1s 1s 91
69 Retry count display erase 0 1 0 91
75
Reset selection/disconnected PU detection/
PU stop selection
0 to 3, 14 to 17 1 14 92
77 Parameter write selection 1, 2 1 2 94
80 Voltage control proportional gain 0 to 1000% 1% 100% 79
81 Voltage control integral gain 0 to 1000% 1% 100% 79
82 Current control proportional gain 0 to 200% 1% 100% 95
83 Current control integral gain 0 to 200% 1% 100% 95
117 PU communication station number 0 to 31 1 0 97
118 PU communication speed 48, 96, 192, 384 1 192 97
119 PU communication stop bit length 0, 1, 10, 11 1 1 97
120 PU communication parity check 0, 1, 2 1 2 97
121 Number of PU communication retries 0 to 10, 9999 1 1 97
123 PU communication waiting time setting 0 to 150ms, 9999 1ms 9999 97
124 PU communication CR/LF selection 0, 1, 2 1 1 97
145 PU display language selection 0 to 7 1 0 117
168
Parameter for manufacturer setting. Do not set.
169
269
342 Communication EEPROM write selection 0, 1 1 0 116
500  Communication error execution waiting time 0 to 999.8s 0.1s 0s 115
501 
Communication error occurrence count
display
0 1 0 115
502  Stop mode selection at communication error 0, 3 1 0 115
542 ,, Communication station number (CC-Link) 1 to 64 1 1 109
543 ,, Baud rate (CC-Link) 0 to 4 1 0 109
544 , CC-Link extended setting 0, 1, 12 1 0 109
C0(900) FM terminal calibration 118
C1(901) AM terminal calibration 118
989 Parameter copy alarm release
10/100
1 10/100 121
990 PU buzzer control 0, 1 1 1 117
991 PU contrast adjustment 0 to 63 1 58 117
Pr. CL Parameter clear 0, 1 1 0 120
ALLC All parameter clear 0, 1 1 0 120
Er.CL Fault history clear 0, 1 1 0 134
PCPY Parameter copy 0, 1, 2, 3 1 0 121
Parameter
Name Range
Increments
Initial
value
Refer to
page
Customer
setting
HC2.book 74 ページ 2012年11月19日 月曜日 午前10時52分