Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
89
3
PARAMETERS
Description of parameters
(6) Monitor switching with input terminal (Pr. 50, Pr. 52, Pr. 54)
Monitoring item can be switched by ON/OFF of terminals X1 and X2.
By setting 1 to 4 to the four digits of Pr. 52 (Pr. 54, Pr. 50), monitor can be switched by the terminals.
Number set in each digits represents the following monitor.
In the initial setting (1234), the monitor changes according to the input terminal status as shown below.
3.4.14 Operation selection at instantaneous power failure (Pr. 57)
If restart after instantaneous power failure is activated at the inverter side, set Pr. 57 Restart selection = "0" at the converter
side.
When Pr. 57="9999," the inverter output is stopped by the fault signal "E.IPF" from the converter even though the automatic
restart after instantaneous power failure is activated in the inverter.
Pr. 50, Pr. 52, Pr. 54 Setting Monitoring Item
1 Input current monitor
2 Bus voltage monitor
3 Input voltage monitor
4 Input power monitor
X1 OFF ON OFF ON
X2 OFF OFF ON ON
Monitoring item
1
Input current monitor
2
Bus voltage monitor
3
Input voltage monitor
4
Input power monitor
When an instantaneous power failure occurs, the converter can restart at the power restoration.
Parameter
Number
Name Initial value Setting range Description
57 Restart selection 9999
0
Restarts at the power restoration after an
instantaneous power failure
9999 Does not restart
CAUTION
The motor and machine will start suddenly after occurrence of an instantaneous power failure (after the reset
time has elapsed). Stay away from the motor and machine when automatic restart after instantaneous power
failure has been selected.
If the automatic restart after instantaneous power failure function has been selected, apply the CAUTION
stickers, which are supplied with the Instruction Manual of the inverter, to easily visible places.
1st digit
2nd digit
3rd digit
4th digit
1st digit 2nd digit 3rd digit 4th digit
Pr. 50, Pr. 52, Pr. 54 =
Status of X1
Status of X2
OFF ON OFF ON
OFF OFF ON ON
HC2.book 89 ページ 2012年11月19日 月曜日 午前10時52分