Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
73
3
PARAMETERS
Parameter list
3.3 Parameter list
REMARKS
indicates simple mode parameters.
The parameters shaded in allow their settings to be changed during operation even if "1" (write disabled) is set to Pr. 77
Parameter write selection.
Parameter
Name Range
Increments
Initial
value
Refer to
page
Customer
setting
0 Simple mode selection 0, 9999 1 0 75
1 Maximum power supply frequency 60Hz (Read only) 60Hz 75
2 Minimum power supply frequency 50Hz (Read only) 50Hz 75
3 ROH terminal function selection
0 to 5, 9999
1576
4 SOF terminal function selection 1 0 76
5 X1 terminal function selection 1 1 76
6 X2 terminal function selection 1 2 76
7 RES terminal function selection 1 3 76
8 SOF input selection 0, 1, 2 1 0 77
9 OH input selection 0, 1 1 0 77
10 RDY signal logic selection 0, 100 1 100 78
11 RSO terminal function selection
0 to 16, 98, 99, 100 to 116, 198,
199, 9999
1178
12 CVO terminal function selection 1 2 78
13 Y1 terminal function selection 1 3 78
14 Y2 terminal function selection 1 4 78
15 Y3 terminal function selection 1 5 78
16 ABC terminal function selection 1 99 78
22 Current limit level 0 to 220% 0.1% 150% 79
23 Current limit level (regenerative) 0 to 220%, 9999 0.1% 9999 79
24 OL signal output timer 0 to 25s, 9999 0.1 0 79
25 Input current detection level 0 to 220% 0.1% 150% 80
26 Input current detection signal delay time 0 to 10s 0.1s 0s 80
27 Input current detection signal retention time 0 to 10s, 9999 0.1s 0.1s 80
28 Input current detection operation selection 0, 1 1 0 80
29 Zero current detection level 0 to 220% 0.1% 5% 80
30 Zero current detection time 0 to 1s 0.01s 0.5s 80
31 Life alarm status display 0 to 15 (Read only) 1 0 81
32 Inrush current limit circuit life display 0 to 100% (Read only) 1% 100% 81
33 Control circuit capacitor life display 0 to 100% (Read only) 1% 100% 81
34 Maintenance timer 0 (1 to 9998) 1 0 82
35 Maintenance timer alarm output set time 0 to 9998, 9999 1 9999 82
36 Cooling fan operation selection 0, 1 1 1 83
44
Instantaneous power failure detection signal
clear
0, 9999 1 9999 83
45 AM output filter 0 to 5s 0.01s 0.01s 84
46 Watt-hour meter clear 0, 10, 9999 1 9999 86
47 Energization time carrying-over times Read only 1 0 86
48
Cumulative power monitor digit shifted
times
0 to 4, 9999 1 9999 86
49
Power supply frequency monitoring
reference
45Hz to 65Hz 0.01Hz 60Hz 84
50 AM terminal function selection 1 to 3, 5, 6, 7, 21, 1111 to 4444 1 1234 86
51 Input power monitoring reference
0 to 100kW/0 to 3600kW

0.01kW/
0.1kW

Rated
power
84
52 DU/PU main display data selection 0, 5 to 10, 25, 1111 to 4444 1 1234 86
53 Input voltage monitoring reference 0 to 500V 0.1V
220V/
440V

84
54 FM terminal function selection 1 to 3, 5, 6, 7, 21, 1111 to 4444 1 1234 86
55 Bus voltage monitoring reference 0 to 1000V 0.1V
340V/
680V

84
HC2.book 73 ページ 2012年11月19日 月曜日 午前10時52分