Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
77
3
PARAMETERS
Description of parameters
3.4.4 Operation selection of SOF signal and OH signal (Pr. 8, Pr. 9)
<SOF signal input status and Pr. 8 setting for the converter operation >
The converter does not operate at the Pr. 8 = "1" (NC contact) setting while FR-A7NC is not mounted. Set Pr. 8 = "2" (NC contact for external signals, NO
contact for CC-Link communication).
<OH signal input status and Pr. 9 setting for the converter operation >
Operation of SOF signal can be changed by the Pr. 8 setting, and OH signal by the Pr. 9 setting.
Parameter
Number
Name
Initial
Value
Setting
Range
Description
8 SOF input selection 0
0
Turning the SOF signal ON stops the converter operation.
(NO contact)
1
Turning the SOF signal OFF stops the converter operation.
(NC contact)
2
External signal: NC contact
CC-Link communication: NO contact
9 OH input selection 0
0 Turning the OH signal ON trips the converter. (NO contact)
1 Turning the OH signal OFF trips the converter. (NC contact)
SOF Signal Input Status Converter Operation
External
terminal
Virtual terminal
for CC-Link
communication
Pr. 8 = 0 (NO contact) Pr. 8 = 1 (NC contact)
Pr. 8 = 2
(External terminal: NC contact)
(Virtual terminal at CC-Link
communication: NO contact)
OFF OFF Operation continues Operation stops Operation stops
OFF ON Operation stops Operation stops Operation stops
ON OFF Operation stops Operation stops Operation continues
ON ON Operation stops Operation continues Operation stops
OH Signal Input Status
(external terminal)
Converter Operation
Pr. 9 = 0 Pr. 9 = 1
ON
Trips
Operation continues
OFF Operation continues Trips
HC2.book 77 ページ 2012年11月19日 月曜日 午前10時52分