PARAMETERS
Parameter copy and parameter verification
3.6 Parameter copy and parameter verification
(1) Parameter copy
PCPY Setting Description
0 Cancel
1 Copy the source parameters to the operation panel.
2 Write the parameters copied to the operation panel into the destination converter.
3 Verify parameters in the converter and operation panel. (Refer to page 122)
REMARKS
When the copy destination is other than the FR-HC2 series converter or when parameter copy is attempted after the parameter
copy reading was stopped, "model error ( )" appears.
Refer to page 188 for the availability of parameter copy.
When the power is turned OFF or an operation panel is disconnected, etc. during parameter copy writing, write again or check
the setting values by the parameter verification.
After a parameter copy, the operation of the converter is in a stop status. Reset the converter after a parameter copy is
completed.
Parameter settings can be copied to multiple converters.
3.Turn until (parameter copy)
appears.
4.Press to read the currently set value.
" "(initial value) appears.
5.Turn to change it to the setting value
" ".
6.Press to copy the source parameters
to the operation panel.
7.Connect the operation panel to the
copy destination converter.
8.After performing the steps 2 to 5,
turn to change it to " ".
9.Press to write the parameters copied to
the operation panel to the destination converter.
10.When copy is completed,
" " and " " flicker.
11.After writing the parameter values to the copy
destination converter, always reset the converter,
e.g. switch power OFF once, before starting operation.
Display
The parameter
number previously
read appears.
Flickers for about 30s
About 30s later
Flicker ··· Parameter copy complete!!
The frequency flickers
for about 30s
Flicker ··· Parameter copy complete!!
Operation
1.
Connect the operation panel to the
copy source converter.
2.Press to choose the parameter
setting mode.
HC2.book 121 ページ 2012年11月19日 月曜日 午前10時52分