(Standard to comply with: UL 508C, CSA C22.2 No. 14)
(1) General Precaution
The bus capacitor discharge time is 10 minutes. Before starting wiring or inspection, switch power off, wait for more than 10 minutes,
and check for residual voltage between terminal P/+ and N/- with a meter etc., to avoid a hazard of electrical shock.
(2) Environment
Before installation, check that the environment meets following specifications.
 Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure. Ambient Temperature is a temperature outside an enclosure.
 2.9m/s
2
or less for the 160K or higher
(3) Installation
High power factor converter (FR-HC2) and its accessories are open type devices which must be installed inside a separate
and suitable Type 1 enclosure along with the external components (Input reactors, Magnetic Contactor, Pre-Charge
Resistor, Capacitors and Transformer).
Make the necessary wiring connections in accordance with the NEC for installations in North America, CEC for Canada and
any applicable local codes.
For installation in the United States, branch circuit protection must be provided in accordance with the National Electrical
Code and any applicable provincial codes.
For installation in Canada, branch circuit protection must be provided in accordance with the Canadian Electrical Code and
any applicable provincial codes.
Provide the appropriate fuse in accordance with the table below.
Due to Type 1 enclosure variables of size, cooling fans, ventilation and location, be sure to monitor the surrounding air
temperature of the converter to not exceed 50
C. Use additional cooling means as necessary.
Install all appended accessories inside the enclosure.
Appendix 3 Instructions for UL and cUL
Surrounding air
temperature 
-10°C to + 50°C Maximum
(non-freezing)
Enclosure
Ambient humidity
90%RH or less (non-condensing)
Storage temperature
-20°C to + 65°C
Ambience
Indoors (No corrosive and flammable gases, oil mist, dust and dirt.)
Altitude, vibration
Below 1000m, 5.9m/s
2
or less at 10 to 55Hz (directions of X, Y, Z axes) 
Converter model Fuse type Cat. No Manufacturer Rating
200V class
FR-HC2-7.5K UL Recognized High Speed 170M1414 Bussmann 50A, 700 Vac
FR-HC2-15K UL Recognized High Speed 170M1416 Bussmann 80A, 700 Vac
FR-HC2-30K UL Recognized High Speed 170M2666 Bussmann 160A, 700 Vac
FR-HC2-55K UL Recognized High Speed 170M2669 Bussmann 315A, 700 Vac
FR-HC2-75K UL Recognized High Speed 170M2671 Bussmann 400A, 700 Vac
400V class
FR-HC2-H7.5K UL Recognized High Speed 170M1411 Bussmann 25A, 700 Vac
FR-HC2-H15K UL Recognized High Speed 170M1414 Bussmann 50A, 700 Vac
FR-HC2-H30K UL Recognized High Speed 170M1416 Bussmann 80A, 700 Vac
FR-HC2-H55K UL Recognized High Speed 170M2666 Bussmann 160A, 700 Vac
FR-HC2-H75K UL Recognized High Speed 170M2667 Bussmann 200A, 700 Vac
FR-HC2-H110K UL Recognized High Speed 170M2669 Bussmann 315A, 700 Vac
FR-HC2-H160K UL Recognized High Speed 170M2671 Bussmann 400A, 700 Vac
FR-HC2-H220K UL Recognized High Speed 170M3122 Bussmann 550A, 700 Vac
FR-HC2-H280K UL Recognized High Speed 170M4117 Bussmann 700A, 700 Vac
FR-HC2-H400K UL Recognized High Speed 170M5116 Bussmann 1000A, 700 Vac
FR-HC2-H560K UL Recognized High Speed 170M6117 Bussmann 1400A, 700 Vac
Measurement
position
Measurement
position
High power factor converter
5cm 5cm
5cm