Minimum spacing distances inside the enclosure are as follows.
(4) Wiring to the power supply and the motor
(1) Wiring the converter with the inverter
Use the UL listed copper stranded wire (rated at 75°C) for wiring between the inverter and the converter (P and N), and
between the converter and input reactor (R4, S4, T4). When wiring to the terminals, refer to the following table, and use
the UL listed crimp ring terminal employing insulation tubing. Crimp the crimping terminals with the crimping tool
recommended by the terminal manufacturer.
(2) The FR-HCB2 Series unit is a UL Listed Accessory for use only with the following converter.
Converter model
Main Circuit-
Terminal
Screw Size
Recommended Criming
Terminal by JST Mfg.
Co., Ltd.
Recommended Tool by JST
Mfg. Co., Ltd.
Tightening-
Torque (Nm)
Cable Size
AWG or kcmil for R4,
S4, T4, P, N terminals
R4/L14,
S4/L24,
T4/L34
P/+, N/-
Terminal
crimping tool
Crimping head
R4/L14,
S4/L24,
T4/L34
P/+, N/-
200V class
FR-HC2-7.5K M5 8-5 8-5
YF-1, E-4
YET-150-1
2.5 8 8
FR-HC2-15K M6 22-6 22-6 4.4 4 4
FR-HC2-30K M8/M10 60-8 60-10 7.8/14.7 1/0 1/0
FR-HC2-55K M12 150-12 150-12 24.5 300 300
FR-HC2-75K M12 150-12 150-12 24.5 300 300
400V class
FR-HC2-H7.5K M5 5.5-5 2-5 2.5 12 14
FR-HC2-H15K M5 5.5-5 5.5-5 2.5 10 10
FR-HC2-H30K M6 22-6 14-6 4.4 4 6
FR-HC2-H55K M8 60-8 38-6 7.8 1 2
FR-HC2-H75K M10 38-10 38-10 14.7 1 1
FR-HC2-H110K M10 60-10 60-10 14.7 1/0 2/0
FR-HC2-H160K M12 100-12 150-12 24.5 4/0 250
FR-HC2-H220K M12 150-12 100-12 24.5 300 2 250
FR-HC2-H280K M12 200-12 150-12 24.5 400 2 300
FR-HC2-H400K M12 RD200-12 RD200-12 YET-300-1,
YET-300N
24.5 2 400 2 400
FR-HC2-H560K M12 RD325-12 RD325-12 24.5 3 600 3 600
FR-HCB2 Series unit Applicable Converter
200V class
FR-HCB2-7.5K FR-HC2-7.5K
FR-HCB2-15K FR-HC2-15K
FR-HCB2-30K FR-HC2-30K
FR-HCB2-55K FR-HC2-55K
FR-HCB2-75K FR-HC2-75K
400V class
FR-HCB2-H7.5K FR-HC2-H7.5K
FR-HCB2-H15K FR-HC2-H15K
FR-HCB2-H30K FR-HC2-H30K
FR-HCB2-H55K FR-HC2-H55K
FR-HCB2-H75K FR-HC2-H75K
FR-HCB2-H110K FR-HC2-H110K
FR-HCB2-H160K FR-HC2-H160K
FR-HCB2-H220K FR-HC2-H220K
Converter
(FR-HC2)
Input
reactor
1, 2
(FR-HCL21,
FR-HCL22)
Outside
box
(FR-HCB2)
500mm or
more
500mm or
more
100mm or
more
100mm or
more
500mm or
more
100mm or
more
100mm or
more
500mm or
more
500mm or
more
100mm or
more
100mm or
more
HC2.book 192 ページ 2012年11月19日 月曜日 午前10時52分