40
Wiring of main circuit (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K)
(8) Wiring of outside box and high power factor converter
Use the cable shown in the below table for the connection.
Converter terminals ROH and SD are used for the control signal for the inrush current limit circuit inside the outside box.
Always connect them to the outside box. Failure to do so will cause internal circuit breakage of the outside box.
Connect the output from the MC start command terminals (88R, 88S) to the terminals (88R, 88S) of the outside box.
<Wiring example of 7.5K>
The terminal arrangement in the outside box differs by capacity. Check the terminal arrangement on 6.3 Outline dimensions (refer to page 150).
Cable gauge
0.75 to 1.25mm
2
Outside box Converter
ROH1
ROH2
ROH
SD
88R
88S
88R
88S
Total wiring
length
10m or less
(1)
(2)
(3)
R2
S2
T2
(A2)
(A1)
R1/L11 S1/L21
Converter
P/+
N/-
88R
88S
A
CVORSORDY
NCNCNC
SENCNCNC
B C NC AM
PCPCY1
PCY2SESE SDSDSDFM
5X1X2
ROHSOFRES
NC
Outside box
ROH2
ROH1 88R
88S
R4
/L14
S4/
L24
T4/
L34
R/
L1
S/
L2
T/
L3
88R
88S
A
CVORSORDY
NCNCNC
SENCNCNC
B C NC AM
PCPCY1
PCY2SESE SDSDSDFM
5X1X2
ROHSOFRES
NC
To 88R
of the
outside box
To 88S
of the
outside box
To ROH2
of the
outside box
To ROH1
of the
outside box
HC2.book 40 ページ 2012年11月19日 月曜日 午前10時52分