Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
148
Rated specifications
6.1 Rated specifications
200V
400V
 Model name of the 400V class ends with H.
 The permissible voltage imbalance ratio is 3% or less. (Imbalance ratio = (highest voltage between lines - average voltage between three lines ) / average
voltage between three lines 100)
 DC output capacity when the input voltage is 200VAC (400V for the 400V class)
 Change the MC power supply stepdown transformer tap according to the input voltage. (Refer to page 51)
 The % value of the overload current rating indicates the ratio of the overload current to the converter's rated input current. For repeated duty, allow time for
the converter and the inverter to return to or below the temperatures under 100% load.
 The protective structure is IP40 for FR-DU07-CNV (except the PU connector) and IP00 for the outside box (220K or lower) and the reactor regardless of
their capacities.
 When the hook of the converter front cover is cut off for installation of the plug-in option, the protective structure changes to the open type (IP00).
 Mass of FR-HC2 alone.
Model name FR-HC2-K 7.5 15 30 55 75
Applicable inverter capacity (kW) 7.5 15 30 55 75
Rated output capacity (kW)
 10.7 19.8 38 71 92
Rated input voltage (V) Three-phase 200V to 220V 50Hz/200V to 230V 60Hz

Rated input current (A) 33 61 115 215 278
Overload current rating
 150% 60s
Permissible power supply voltage fluctuation
170V to 242V 50Hz
170V to 253V 60Hz
170V to 230V
50Hz/60Hz
Permissible power supply frequency fluctuation 5%
Input power factor 0.99 or more (when load ratio is 100%)
Power supply capacity (kVA) 14 25 47 88 110
Protective structure of the converter
 Enclosed type (IP20)  Open type (IP00)
Cooling system Forced air cooling
Approximate mass (kg)
 7 12243953
Model name FR-HC2-HK  7.5 15 30 55 75 110 160 220 280 400 560
Applicable inverter capacity (kW) 7.5 15 30 55 75 110 160 220 280 400 560
Rated output capacity (kW)
 11.0 20.2 37 73 92 135 192 264 336 476 660
Rated input voltage (V)
 Three-phase 380V to 460V 50Hz/60Hz 
Rated input current (A) 17 31 57 110 139 203 290 397 506 716 993
Overload current rating
 150% 60s
Permissible power supply voltage
fluctuation
323V to 506V 50/60Hz 323V to 460V 50/60Hz
Permissible power supply
frequency fluctuation
5%
Input power factor 0.99 or more (when load ratio is 100%)
Power supply capacity (kVA) 14 26 47 90 113 165 235 322 410 580 804
Protective structure of the
converter

Enclosed type
(IP20)

Open type (IP00)
Cooling system Forced air cooling
Approximate mass (kg)
 9 9 26 43 37 56 120 120 160 250 250
HC2.book 148 ページ 2012年11月19日 月曜日 午前10時52分