Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
7
1
OUTLINE
Converter and peripheral devices
1.2 Converter and peripheral devices
Earth
(Ground)
Three-phase AC power supply
Use within the permissible power
supply specifications of the converter.
High power factor converter
(FR-HC2)
Install and wire correctly.
Do not install the moulded case circuit
breaker (MCCB) between terminals P
and P, or N and N of the converter
and the inverter.
Inverter
Confirm that this is a FR-HC2
supporting inverter. (Refer to the
inverter catalogs for compatible
inverters.)
Connect an inverter that corresponds
with the each capacity of the converter.
Match the control logic (sink logic /
source logic) of the converter and the
inverter.
Motor
Connect the motor corresponds to the
each capacity.
Magnetic contactor (MC)
Install the magnetic contactor to
ensure safety.
Do not use this magnetic contactor to
start and stop the high power factor
converter and the inverter. Doing so will
shorten the life of the inverter and the
converter.
Moulded case circuit breaker (MCCB) or
earth leakage current breaker (ELB),
fuse
The breaker must be selected carefully since
an inrush current flows in the converter at
power ON.
Reactor 1 (FR-HCL21)
Confirm that the capacity of the reactor
is selected according to the capacity of
the converter.
Reactor 2 (FR-HCL22)
Confirm that the capacity of the reactor
is selected according to the capacity of
the converter.
R4S4T4
Devices connected to the output
Do not install a power factor correction capacitor,
surge suppressor or radio noise filter on the output
side of the inverter. When installing a moulded case
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground)
the motor and inverter.
PN
Fuse
Installation of a fuse is recommended
for safety.
Select a fuse according to the
connected motor capacity.
Outside box (FR-HCB2)
Check that the capacity of the outside box
matches with the capacity of the high power
factor converter.
Outside box is not available for 280K or higher.
Connect filter capacitors, inrush current limit
resistors, and magnetic contactors.
(Refer to page 35, 49)
(Refer to page 35, 49)
(Refer to page 34, 47)
(Refer to page 60)
(Refer to page 34)
(Refer to page 12)