Mitsubishi Electronics FR-HC2 Marine Battery User Manual


 
52
Wiring of main circuit (FR-HC2-H400K, H560K)
(6) Wiring the power supply and inverter
Connect the inverter control power supply directly to the power supply without connecting a converter in between.
(7) Wiring filter capacitor alarm detector and converter
Use the cable shown in the below table for the connection.
Before wiring, read the Instruction Manual appended to the filter capacitor alarm detector carefully.
<Wiring example of 400K>
<Wiring example of 560K>
 Connect the wiring to the terminals R5/L15 and S5/L25 of the MC power supply stepdown transformer by placing parallel with the wiring of (5) Wiring reactor
1 and converter (Refer to page 51).
 Install the mini relay using the provided mini relay terminal block (PYF14T) and the mini relay clip (PYC-A1).
NOTE
Refer to the Instruction Manual of the inverter, and remove the jumpers across terminals R/L1 and R1/L11 and across
terminals S/L2 and S1/L21 in the inverter main circuit.
Always connect the power supply to the inverter. It supplies power to the inverter's control power and large-capacity
cooling fan. If not connected, the inverter may come to a trip or be damaged.
Cable gauge
2mm
2
Power
supply
Inverter control
power supply
R1
S1
MCCB
R1/L11
S1/L21
Cable gauge
0.75 to 2mm
2
ROH
SD
MC
Small
R/
L1
S/
L2
T/
L3
R/L1
S/L2
R5/L15
S5/L25
V1
AC410V
V2
AC430V
V3
AC470V
MC1
MC2
MC3
MC
Bu2
R2/
L12
S2/
L22
T2/
L32
Power
Supply
Reactor 1
(FR-HCL21-H400K)
Stepdown
transformer
(1PH 630VA)
Filter capacitor alarm
detector (NC contact) 2
Buffer relay for
filter capacitor
alarm detectors
(SR-N4)
Filter capacitors 2
(FR-HCC2-H400K)
Converter
(FR-HC2-H400K)
Auxiliary contact for
inrush current limit MCs
(NO contact) 3
Mini relay for
filter capacitor
alarm detector
(MYQ4Z AC200/220)
Limit resistor (with thermostat)
(NC contact) 3


R/
L1
S/
L2
T/
L3
R2/
L12
S2/
L22
T2/
L32
ROH
SD
MC
Small
Filter capacitors 3
(FR-HCC2-H560K)
R/L1
S/L2
R5/L15
S5/L25
V1
AC410V
V2
AC430V
V3
AC470V
MC1
MC2
MC3
MC
Bu2
Power
Supply
Reactor 1
(FR-HCL21-H560K)
Stepdown
transformer
(1PH 630VA)
Converter
(FR-HC2-H560K)
Filter capacitor alarm
detector (NC contact) 3
Buffer relay for
filter capacitor
alarm detectors
(SR-N4)
Auxiliary contact for
inrush current limit MCs
(NO contact) 3
Mini relay for
filter capacitor
alarm detector
(MYQ4Z AC200/220)
Limit resistor (with thermostat)
(NC contact) 3

