Troubleshooting with the DeviceNet Unit Indicators Section 9-1
9-1 Troubleshooting with the DeviceNet Unit Indicators
9-1-1 Determining Operating Status from the Indicators
The following table shows the status of the MS and NS indicators and the 7-
segment display during normal operation.
Indicator status Network/Unit status Comments
MS NS 7-segment
OFF OFF OFF Initializing with PC Initialization processing with the PC is in progress.
Restart the DeviceNet Unit if this status continues
for an extended period of time. Replace the CPU
Unit and/or DeviceNet Unit if the problem is not cor-
rected by restarting.
ON
(green)
OFF Masters node
address
(flashing)
Checking for node address
duplication
The node address duplication check is performed
after initialization.
ON
(green)
Flashing
(green)
Masters node
address
(flashing)
Waiting for remote I/O com-
munications
The Unit will have this status until remote I/O com-
munications are performed with the master or slave
function. (When both functions are operating, the
Unit will have this status until remote I/O communi-
cations are performed with either function.)
Masters node
address
Waiting for message commu-
nications connection
The Unit will have this status when both the master
and slave functions are disabled and the Unit is
waiting for a connection by message communica-
tions.
ON
(green)
ON
(green)
Masters node
address
Remote I/O or message com-
munications in progress.
This is the normal display when the master and/or
slave is active.
ON
(green)
ON
(green)
- - (flashing) Scan list operation in
progress.
The scan list is being saved in flash memory or the
scan list is being cleared.