Omron CJ1W-DRM21 Marine RADAR User Manual


 
66
Allocated CIO Area Words Section 3-2
06 Slave
Enable
Switch
OFF
ON
User Enables slave communications. (The Unit automatically
restarts.)
To use fixed allocations, turn this switch ON after turning
ON a Slave Fixed Allocation Setting Switch (word n+1,
bits 08 to 10). To used user-set allocations, turn this
switch ON after turning ON the User Setting Switch
(word n+1, bit 11).
Once enabled, the Unit will function as a slave regard-
less of whether the power is turned OFF and back ON
again until the Slave Stop Switch (word n+1, bit 07) is
turned ON.
Note 1. Slave communications are enabled in the
default setting.
2. If this bit is turned ON with Slave enabled, a
Unit status error will occur and a C2 error will
be displayed on the 7-segment display. The
7-segment display will go out automatically
after 30 seconds.
Pro-
gram
mode
Dis-
abled
Slave
disabled
OFF Unit Returns to OFF at the start of slave communications.
07 Slave Stop
Switch
OFF
ON
User Stops slave communications. (The Unit automatically
restarts.) Turn this switch ON if the Unit will be used only
for master communications.
Pro-
gram
mode
Dis-
abled
Slave
disabled
OFF Unit Returns to OFF after slave communications stop.
Bit Name Status Con-
trolled by
Unit operation Operation
conditions
Default
setting
CPU
Unit
oper-
ating
mode
Slave
func-
tion