Omron CJ1W-DRM21 Marine RADAR User Manual


 
231
Allocation Differences from C200H DeviceNet Master Units Appendix A
Communi-
cations
Error Flag
IR 2001+
(10 × unit
No.)
Unit No. 0
to 9: IR
101+(10 ×
unit No.)
Unit No. A
to F: IR
401+(10 ×
unit No.
10)
06 Communi-
cations
Error Flag
CIO 1524+
(25 × unit
No.)
06 This is the same as the Remote I/O
Communications Error Flag (word
n+12, bit 02).
Verification
Error Flag
07 Verification
error
07 This is the same as the Verification
Error Flag in word n+12, bit 00.
I/O Data
Communi-
cations Not
Running
Flag
08 I/O Data
Communi-
cations Not
Running
Flag
08 This operates in the reverse way of
the Remote I/O Communications Flag
(word n+11 bit 01).
Scan List
Operation
Completed
Flag
09 Reserved
for system
use
09 ---
Scan List
Operation
Error Flag
10 Reserved
for system
use
10 ---
Communi-
cations
Error Stop
Cleared
Flag
11 Reserved
for system
use
11 ---
Message
Communi-
cations
Enable Flag
12 Message
Communi-
cations Per-
mitted Flag
12 The same as the Online Flag in word
n+11, bit 00.
Note When executing message com-
munications instructions
(SEND/RECV/CMND) from the
ladder program, use an AND of
input conditions for the Network
Communications Enabled Flag
in the CPU Unit (A20200 to
A20207) and this bit.
Scan List
Disabled
Flag
13 Scan List
Disabled
Flag
13 The same as operation as the Scan
List Disabled Flag (word n+11, bit 04).
Error Flag 14 Error Flag 14 This bit turns ON if bit 00, 01 or 03 to
07 in this word (n+24) turns ON.
I/O Data
Communi-
cations Flag
15 I/O Data
Communi-
cations
Flag
15 The same as I/O Data Communica-
tions Flag (word n+12 bit 15).
Names for
C200H
DeviceNet
Master
Unit
Master
Status
Area 1
C200H DeviceNet Master Unit Names for
CS/CJ-
series
DeviceNet
Unit Mas-
ter
Replace-
ment Sta-
tus 1
CS/CJ-series
DeviceNet Unit
Details and CS1W-DRM21/CJ1W-
DRM21 status
Word address Bit CS/CJ-
series
word
address
Bit
CS/CJ
Series
C200HX/
HG/ HE,