Omron CJ1W-DRM21 Marine RADAR User Manual


 
70
Allocated CIO Area Words Section 3-2
Remote I/O communications will restart if a user turns OFF a bit that is ON.
More than one of these switches may be turned ON at the same time. If the
switch for a slave that is not using remote I/O communications is turned ON, it
will be ignored.
A Unit that has been disconnected can still perform message communica-
tions.
Turning ON this bit does not effect the communications cycle time (except that
it increases blank time in the communications cycle).
Note All Disconnect/Connect Switches are cleared and return to OFF
when the power is turned OFF. If required, write the ladder program
to turn them back ON when the power is turned ON.
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
31 30 29 28 27 26 25 24 23 22 21 20 19 18 17 16
47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32
63 62 61 60 59 58 57 56 55 54 53 52 51 50 49 48
n+6
n+7
n+8
n+9
Bit15 Bit14 Bit13 Bit12 Bit11 Bit10 Bit09 Bit08 Bit07 Bit06 Bit05 Bit04 Bit03 Bit02 Bit01 Bit00
Bit Name Status Controlled
by
Unit operation
Disconnect/
Connect
Switch
ON User Stops remote I/O communications for the corresponding Slave.
OFF User Starts remote I/O communications for the corresponding Slave.