Omron CJ1W-DRM21 Marine RADAR User Manual


 
62
Allocated CIO Area Words Section 3-2
02 Remote I/
O Com-
munica-
tions Start
Switch
OFF
ON
User Starts remote I/O communications.
Note 1. The switch is ignored if remote I/O commu-
nications are already running.
2. This switch is used to restart remote I/O
communications if they are stopped by a
communications error.
3. Communications with a slave will fail even if
remote I/O communications are started if
the Disconnect/Connect Switch (corre-
sponding bit in words n+6 to 9) is ON (1:
Connect).
--- En-
abled
--- None
OFF Unit Returns to OFF at the start of remote I/O communica-
tions.
Note This switch will stop remote I/O communications
if DIP switch pin 3 on the front panel (remote I/O
communications start/stop with a communica-
tions error) is ON (stop) and there is an ongoing
communications or send error.
03
Remote I/O
Communi-
cations
Start
Switch
OFF
ON
User This switch functions the same as bit 02 above.
Note This switch is used to ensure compatibility
between the software switches and C200H
DeviceNet Master (C200HW-DRM21-V1).
---
En-
abled
---
OFF Unit
04 Remote I/
O Com-
munica-
tions Stop
Switch
OFF
ON
User Stops remote I/O communications.
Once remote I/O communications have been stopped,
they will remain stopped until the Unit has been
restarted or the remote I/O communications have been
restarted (i.e., until the Remote I/O Communications
Start Switch is turned ON).
Note 1. The switch is ignored if remote I/O commu-
nications are already stopped.
2. Message communications will remain
enabled even if remote I/O communications
have stopped.
--- En-
abled
---
OFF Unit Returns to OFF when remote I/O communications
stop.
05 Reserved
by system
--- --- --- --- --- --- ---
Bit Name Status Con-
trolled
by
Unit operation Operation condi-
tions
Default
setting
CPU
Unit
oper-
ating
mode
Mas-
ter
func-
tion
Scan
list
sta-
tus