Troubleshooting with the DeviceNet Unit Indicators Section 9-1
DeviceNet Unit Response
Records the error in the error log.
The Unit will go offline and communications will be disabled. Error
responses will be returned to all communications requests.
The exchange of data with the CPU Unit will continue.
Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)
Bit 14 (Error Flag) and bit 01 (the Node Address Duplicated/Bus Off Flag) will
be ON.
CIO Area Flags Allocated to DeviceNet Unit
Bits 00 and 06 of n+10 (the Unit Error Flag and Duplicated Node Address
Flag) will be ON.
Correction
Check the node addresses set on other nodes in the network. Correct the set-
tings to eliminate the duplication and restart the DeviceNet Units.
Bus Off Detected
Likely Cause
A Bus Off condition was detected.
DeviceNet Unit Response
Records the error in the error log.
The Unit will go offline and communications will be disabled. Error
responses will be returned to all communications requests.
The exchange of data with the CPU Unit will continue.
Flags Allocated for C200H DeviceNet Master Unit (CIO n+24)
Bit 14 (Error Flag) and bit 01 (the Node Address Duplicated/Bus Off Flag) will
be ON.
CIO Area Flags Allocated to DeviceNet Unit
Bits 00 and 05 of n+10 (the Unit Error Flag and Bus Off Flag) will be ON.
Correction
Check the following:
Matching master and slave baud rates
Proper cable lengths (trunk and branch lines)
Broken or loose cables
Installation of terminators at both ends of the trunk line
Excessive noise
Memory Access Errors
Message Monitoring
Timer List Logic Error
Likely Cause
There is an error in the contents of the message monitoring timer list stored in
non-volatile memory.
7-segment MS indicator NS indicator Error log (Hex)
F1 --- Red (lit) 0340
7-segment MS indicator NS indicator Error log (Hex)
E6 Red (flashing) --- 021A