241
Appendix C
FINS Commands and Responses for
DeviceNet Units
List of Command Codes
Refer to SYSMAC CS/CJ Series Communication Commands Reference Man-
ual (W342) for details on end codes.
RESET (0403)
Resets (restarts) the DeviceNet Unit.
Command Block
Resets the DeviceNet Unit.
Response Block
There are no responses for this command
End Code
Explanation
• Resets the DeviceNet Unit.
• A communications error has occurred at the Slave but the Slave will
restore after the DeviceNet Unit has started up.
• The remote device communicating the message may have timed out but
communications can be performed normally after the DeviceNet Unit has
started up.
READ CONTROLLER INFORMATION (0501)
Reads the following DeviceNet Unit information.
• Model
• Version
• Node address
Command type Command code Reference page
RESET 0403 241
CONTROLLER DATA READ 0501 241
CONTROLLER STATUS READ 0601 242
ECHOBACK TEST 0801 243
ERROR LOG READ 2102 244
ERROR LOG CLEAR 2103 245
End code (hex) Contents
1001 The command length exceeds maximum
command length.
Command code