86
Allocated DM Area Words Section 3-3
Areas and Word Ranges
Setting Results
Name Range Details
Slave OUT 1 area See Areas
and Word
Ranges.
Specifies the OUT 1 area. The OUT 1
area is not available if this is set at 0.
First word in the Slave
OUT 1 area
Specifies the first word in the OUT 1 area.
OUT 1 area size 00 to C8
Hex
(0 to 200
bytes)
Specifies the size of the OUT 1 area in
bytes. The OUT 1 area is not allocated
when set to 00 Hex.
Slave IN 1 area See Areas
and Word
Ranges.
Specifies the IN 1 area. The IN 1 area is
not allocated when set to 00 Hex.
First word in the Slave IN 1
area
Specifies the first word in the IN 1 area.
IN 1 area size 00 to C8
Hex
(0 to 200
bytes)
Specifies the size of the IN 1 area in
bytes. The IN 1 area is not allocated
when set to 00 Hex.
Setting results See Setting
Results.
Shows the setting results.
Code Name Word range
00 Hex CIO Area (CIO) The area is not used.
01 Hex Data Memory (DM) 0000 to 17FF Hex (0 to 6143)
03 Hex Work Area (WR) 0000 to 7FFF Hex (0 to 32767)
04 Hex Holding Relay (HR) 0000 to 01FF Hex (0 to 511)
05 Hex Expansion Data Memory (EM) 0000 to 01FF Hex (0 to 511)
08 to 14
Hex
Bank 0 to bank C (13 banks) 0000 to 7FFF Hex (0 to 32767) for
all banks
Code Description Details
0000 Hex Completed nor-
mally
---
1101 Hex No area Incorrect area setting.
1103 Hex Address range
specification error
The first word is outside the setting range.
110C Hex Parameter error The OUT 1 or IN 1 area size exceeds
200 bytes.
The OUT 1 and IN 1 area size is 0.
Both the OUT 1 and IN 1 blocks are set
for no allocations.
1104 Hex Address range
overflow
The allocated area exceeds the valid word
range.
2201 Hex Wrong operating
mode
The CPU Unit is not in PROGRAM mode.
2201 Hex Unit busy Service cannot be executed because the
Unit is busy.
2606 Hex Cannot execute
service
The Unit slave communications have not
been disabled.