Omron CJ1W-DRM21 Marine RADAR User Manual


 
84
Allocated DM Area Words Section 3-3
Setting Results
3-3-3 Allocation Size Setup Table
The following allocation size setup tables must be set in the I/O memory in the
CPU Unit to use the Master User Allocations Setup Table.
The number of bytes set in the allocation size setup table are allocated in
word units in order of node addresses for OUT block 1 and then IN block 1.
Set the sizes within a range from 0 to 200 bytes (100 words).
Code Description Details
0000
Hex
Completed normally ---
1101
Hex
No area Incorrect area setting.
The allocated size in the allocation size setup
table is 0.
1103
Hex
Address range specifi-
cation error
The first word is outside the setting range.
110C
Hex
Parameter error The OUT or IN size in the allocation size setup
table exceeds 200 bytes.
Both the OUT and IN blocks are set for no allo-
cations.
No slaves are allocated.
1104
Hex
Address range over-
flow
The block or the allocation size setup table ex-
ceeds the valid word range.
The block is larger than 1,000 bytes.
2201
Hex
Wrong operating
mode
The CPU Unit is not in PROGRAM mode.
2201
Hex
Unit busy Service cannot be executed because the Unit is
busy.
2606
Hex
Cannot execute ser-
vice
The Unit master communications have not been
disabled.
Word
Bit 15 Bit 08 Bit 07 Bit 00
Node address 0 OUT size (bytes)
Node address 0 IN size (bytes)
I
Node address 1 OUT size (bytes)
Node address 1 IN size (bytes)
I+1
Node address 63 OUT size (bytes)
Node address 63 IN size (bytes)
I+63
:
: