Appendix F: Configuring Using HART
February 2015
F.2.4 Learn false echo
The transmitter can be manually told the live Distance (on page 153) is being calculated from a
false target echo and that echo can therefore be ignored. If there is another false target echo,
repeat the learning process again. A maximum of four false echoes can be learnt.
Field Communicator
To ignore a false target echo:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 6: False Echoes (MSP900GH)
or 7: False Echoes (MSP400RH).
4. Select 6: Learn False Echo.
5. Wait three seconds while the transmitter learns to ignore the false echo.
Note
When messages appear, take appropriate action if needed and press “OK”.
Mobrey MCU900 Series control unit
To ignore a false target echo:
1. From the Main Menu screen, select SETUP.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select ENGINEERING.
4. Select FALSE ECHO ACTION, and then Learn False Echo.
5. Follow the on-screen instruction (“Start”) to ignore a false echo.
(Press the Enter ( ) key if prompted to change the mode to “off-line”).
6. Select “Quit” to exit to the previous menu.
Note
See Clear False Echoes on page 143 for how to clear all learned false echoes.
See False Echo Data on page 142 for how to edit existing false echo data.
Use the “Auto Tank Map” feature for automatic learning (page 94).
Fast Keys
2, 2, 6 [or 7], 6
1. Number of False Echoes
2. Distance D910
3. Echo Size D911
4. Target Echoes D913
5. Clear False Echoes
6. Learn False Echo
7. Auto Tank Map
8. False Echo Data
6. Learn False Echo
SAVE
HOME
HELP
0
10.674 ft
75 %
5
(Field Communicator Screen)
Esc=Quit =Start
LEARN FALSE ECHO
(Mobrey MCU901 Screen)