59
Reference Manual
IP2048/RM, Rev AA
Section 5: Service and Troubleshooting
February 2015
To edit and fix the temperature
1. After entering the “Eng” menu (see the note above), press the green button
repeatedly until “t.CAL” is indicated.
2. Press the blue button
to enter the “t.CAL” menu. The display indicates the present
setting.
3. If this setting is correct, press the red button
to exit to the menu.
(The menu option “t.CAL” re-appears”. Press
to get to the next menu).
4. Press the blue button
to start the editing mode. The first digit flashes to indicate it
can now be edited.
5. Press the green button
repeatedly to edit the flashing digit.
6. Press the blue button
to move to the next digit. The digit flashes to indicate it can be
edited.
7. Repeat steps (5) and (6) until the last digit is flashing, and edited as required.
8. Press the blue button
to confirm the new value. (The flashing stops).
9. If the new value is correct, press the red button
to save. The display changes to the
next menu option.
10. If the new value is incorrect, press the blue button
to exit to the menu. (The menu
option “t.CAL” re-appears; re-start at step (2) or press
to get to the next menu.)
5.4.12 Loading factory default values
Screen display: Ld.dEF
It may, occasionally, be necessary to re-set the transmitter parameters to factory default values,
particularly if the data already changed is in question.
To ensure that this operation is not initiated by accident, a specific push-button sequence is
necessary to load factory defaults.
Note
Re-loading factory defaults overwrites all parameters and all site entered data will be
lost.
This menu option is in the engineering menu “Eng”. See “Accessing the engineering
menu” on page 49 or see Figure C-3 on page 79 for a map of the menu structure.