138
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.3.33 Threshold 1 size (P048)
False echoes may occur close to the transmitter face. If they occur outside the Upper Blanking
distance (page 131), the false echo can be ignored by entering the echo size as a percentage and
a time (representing distance). The echo size is set by the parameter Threshold 1 Size (P048).
See “Threshold 1 time (P043)” on page 137 for entering the time (representing distance).
Note
Use the read-only parameter Echo Size (page 154) as a reference for the false echo size.
See also “False echoes under certain ambient operating conditions” on page 62 for
additional information about adjusting the settings of parameters P043 and P048.
Field Communicator
To view or change the threshold size:
1. From the Home screen, select 2: Configure.
2. Select 2: Manual Setup.
3. Select 7: Advanced Processing (MSP900GH) or
Select 8: Advanced Processing (MSP400RH)
4. Select 2: Threshold.
5. Select 7: Threshold 1 Size P048.
6. If a change is required:
(a) Input a new value, and then select “ENTER” to save it.
(b) Press “SEND” to update the transmitter.
Mobrey MCU900 Series control unit
To view or change the threshold size:
1. From the Main Menu screen, select SETUP.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select ENGINEERING.
4. Select ADVANCED.
5. Select Thresh 1 Size.
6. Follow the on-screen instructions to edit and save the new setting. (Press the Enter
( ) key if prompted to change the mode to “off-line”).
7. Select “Quit” to exit to the previous menu.
Fast Keys
2, 2, 7 [or 8], 2, 7
Threshold 1 Size P048
6.0 %
6.0
ESC
DEL ENTER
HELP
w
s
q
a
z
Lock
Shift
@ &
á ü
x
e
d
c
r
f
v
t
g
b
y
h
n
u
j
m
*
-
+
/
.
0
7
4
1
8
5
2
9
6
3
i
k
o
l
FN
(Field Communicator Screen)
Thresh 1 Size P048
4.0%
Esc=Quit =Edit
(Mobrey MCU901 Screen)