Emerson Mobrey MSP400RH and MSP900GH Marine Radio User Manual


 
97
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.2.8 Load defaults
This restores the transmitter parameters to the factory default values for the selected base
units. This is sometimes necessary, particularly if the data held in the transmitter is in doubt.
Note
Restoring the factory defaults values overwrites all site entered data. After loading the
factory defaults, the transmitter automatically re-starts and communication is interrupted
until the re-start is complete.
Field Communicator
To restore the factory default settings of the transmitter:
1. From the Home screen, select 3: Service Tools.
2. Select 4: Maintenance.
3. Select 3: Utilities.
4. Select 2: Load Defaults.
5. When the message “About to restore factory defaults” appears, press “OK” to continue
(or “ABORT” to not continue).
6. Select 1: Yes to restore the factory defaults.
Note
When messages appear, take appropriate action if needed and press “OK”.
Mobrey MCU900 Series control unit
To restore the factory default settings of the transmitter:
1. From the Main Menu screen, select SETUP.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select SYSTEM, and then select DEFAULTS.
4. Follow the on-screen instructions (select “Start” and answer “Yes”) to restore the
factory defaults. Press the Enter ( ) key if prompted to change the mode to
off-line”.
5. Select “Quit” to exit to the previous menu.
Fast Keys
3, 4, 3, 2
Utilities
1. Restart Device
2. Load Defaults
3. Set Base Units
2. Load Defaults
SAVE
HOME
HELP
(Field Communicator Screen)
LOADS FACTORY
DEFAULT VALUES
Esc=Quit =Start
DEFAULTS
(Mobrey MCU901 Screen)