151
Reference Manual
IP2048/RM, Rev AA
Appendix F: Configuring Using HART
February 2015
F.4.5 % of output current (D905)
This indicates the percentage of the 4–20 mA output current in use.
0% represents 4 mA
100% represents 20 mA
Note
When the Poll Address (page 163) is a non-zero number, the transmitter is in multi-drop
mode and the current output is fixed at 4 mA. However, the read-only parameter D905
remains active.
Field Communicator
To view the percentage of current output in use:
1. From the Home screen, select 3: Service Tools.
2. Select 2: Variables.
3. Select 2: Analog Output.
4. Select 3: Percentage of Current Output.
5. When finished, press the Bksp key to exit to the previous menu.
Mobrey MCU900 Series control unit
To view the percentage of current output in use:
1. From the Main Menu screen, select MONITOR.
2. Select the transmitter (e.g. “Tx1:MSP400RH”).
3. Select READINGS, and then select CURRENT.
4. Select% of Current Output.
5. When finished, press the ESC key to exit to the previous menu.
Fast Keys
3, 2, 2, 3
Percentage Current Output - (%)
Value: 90.039
HELP
0
100
75
50
25
(Field Communicator Screen)
% Current Out D905
90.0%
(Mobrey MCU901 Screen)